DLP-A521 Modify Alarm, Condition, and History Filtering Parameters
Return to your originating procedure (NTP).
Step 10
DLP-A521 Modify Alarm, Condition, and History Filtering Parameters
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
At the node, network, or card view, click the Alarms tab, Conditions tab, or History tab.
Step 1
Click the Filter button at the lower-left of the bottom toolbar.
Step 2
The filter dialog box appears, displaying the General tab.
the Conditions and History tabs have similar dialog boxes.
Figure 22-7
In the Show Severity area, click the check boxes for the severities [CR, MJ, MN, or Not-Alarmed (NA)]
Step 3
that you want to show through the alarm filter and be reported at the network level. Leave severity check
boxes deselected (unchecked) to prevent those severities from appearing.
When alarm filtering is disabled, all alarms show.
In the Time area, click the Show alarms between time limits check box to enable it. Click the up and
Step 4
down arrows in the From Date, To Date, and Time fields to modify the period of alarms that is shown.
To modify filter parameters for conditions, click the filter dialog box Conditions tab
Step 5
you do not need to modify them, continue with
Cisco ONS 15454 Procedure Guide, R5.0
22-16
This task changes alarm and condition reporting in all network nodes.
None
DLP-A225 Enable Alarm Filtering, page 19-17
DLP-A60 Log into CTC, page 17-66
As needed
Onsite or remote
Retrieve or higher
Alarm Filter Dialog Box General Tab
Figure 22-7
shows the Alarm Filter dialog box;
Step
6.
Chapter 22
DLPs A500 to A599
(Figure
22-8). If
October 2005