DLP-A37 Install the XCVT or XC10G Cards
Note
Note
Note
Verify that the ACT/STBY LED is green for active.
Step 5
Use the latches/ejectors to firmly slide the second cross-connect card along the guide rails until the card
Step 6
plugs into the receptacle at the back of the slot (Slot 8 or 10).
Step 7
Verify that the card is inserted correctly and close the latches/ejectors on the card.
Note
Step 8
Verify the LED activity:
The red LED turns on for 20 to 30 seconds.
The red LED blinks for 35 to 45 seconds.
The red LED turns on for 5 to 10 seconds.
All LEDs blink once and turn on.
The ACT/STBY LED turns on.
Note
Note
Note
Step 9
Verify that the ACT/STBY LED is amber for standby.
Return to your originating procedure (NTP).
Step 10
Cisco ONS 15454 Procedure Guide, R5.0
17-46
If you insert a card into a slot provisioned for a different card, all LEDs turn off.
If the red FAIL LED does not turn on, check the power.
If the red FAIL LED is on continuously or the LEDs act erratically, the card is not installed
properly. Remove the card and repeat Steps
It is possible to close the latches/ejectors when the card is not completely plugged into the
backplane. Ensure that you cannot insert the card any further.
If you insert a card into a slot provisioned for a different card, all LEDs turn off.
If the red FAIL LED does not turn on, check the power.
If the red FAIL LED is turned on continuously or the LEDs act erratically, the card is not
installed properly. Remove the card and repeat Steps
1
to 4.
6
through 8.
Chapter 17
DLPs A1 to A99
March 2005