DLP-A36 Install the TCC2/TCC2P Cards
Note
Note
Note
Note
Verify that the ACT/STBY LED is green if this is the powered-up TCC2/TCC2P card installed, or yellow
Step 5
for standby if this is the second powered-up TCC2/TCC2P. The IP address, temperature of the node, and
time of day appear on the LCD. The default time and date is 12:00 AM, January 1, 1970.
The LCD cycles through the IP address, node name, and software version. Verify that the correct
Step 6
software version displays on the LCD.
If the LCD shows the correct software version, continue with
Step 7
correct software version, upgrade the software or remove the TCC2/TCC2P card and install a
replacement card.
Refer to the release-specific software upgrade document to replace the software. To exchange the
TCC2/TCC2P card, see the Cisco ONS 15454 Troubleshooting Guide.
Repeat Steps
Step 8
Tip
Cisco ONS 15454 Procedure Guide, R5.0
17-44
All LEDs (including the CRIT, MAJ, MIN, REM, SYNC, and ACO LEDs) blink once and turn
off for about 10 seconds.
Both green PWR LEDs turn on for 5 seconds. The PWR LEDs then turn red for 2 to 3 minutes
before going to steady green.
The yellow ACT/STBY turns on and the PWR LEDs turn red for 2 to 3 minutes. (The Sync LED
might be green at this time.)
The yellow ACT/STBY LED turns on. (The ACT/STBY LED might take several minutes to turn
on while the DCC processor boots.)
It might take up to 3 minutes for the A and B power alarms to clear.
Alarm LEDs might be on; disregard alarm LEDs until you are logged into CTC and can view the
Alarms tab.
If you are logged into CTC, the SFTWDOWN alarm might appear as many as two times while
the TCC2P card initializes. The alarm should clear after the card completely boots.
If the FAIL LED is on continuously, see the tip below about the TCC2P card automatic upload.
1
through
7
for the redundant TCC2/TCC2P card.
If you install a standby TCC2/TCC2P card that has a different software version than the active
TCC2/TCC2P card, the newly installed standby TCC2/TCC2P card automatically copies the
software version from the active TCC2/TCC2P card. You do not need to do anything in this
situation. However, the loading TCC2/TCC2P card does not boot up in the normal manner. When
the standby card is first inserted, the LEDs follow most of the sequence listed in
the red FAIL LED turns on for about 5 seconds, the FAIL LED and the ACT/STBY LED begin
to flash alternately for up to 30 minutes while the new software loads onto the active
TCC2/TCC2P card. After loading the new software, the upgraded TCC2/TCC2P card's LEDs
repeat the sequence from
Step
4, and the amber ACT/STBY LED turns on.
Chapter 17
Step
8. If the LCD does not show the
DLPs A1 to A99
Step
4. After
March 2005