DLP-A16 Connect the Office Ground to the ONS 15454
DLP-A16 Connect the Office Ground to the ONS 15454
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Verify that the office ground cable (#6 AWG stranded) is connected to the top of the bay according to
Step 1
local site practice.
Attach one end of the shelf ground cable (#10 AWG) to the right side of the backplane ground nut. See
Step 2
Figure 17-9
Note
Figure 17-9
Step 3
Attach the other end of the shelf ground cable to the bay.
Return to your originating procedure (NTP).
Step 4
Cisco ONS 15454 Procedure Guide, R5.0
17-18
This task connects ground to the ONS 15454 shelf.
#2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws
Power cable (from fuse and alarm panel to assembly), #10 AWG, copper
conductors, 194 degrees Fahrenheit [90 degrees Celsius])
Ground cable #6 AWG stranded
Listed pressure terminal connectors such as ring and fork types; connectors
must be suitable for #10 AWG copper conductors
DLP-A10 Remove the Lower Backplane Cover, page 17-10
Required
Onsite
None
for the location of the ground on the backplane.
When terminating a frame ground, use the Kepnut provided with the ONS 15454 and tighten it
to a torque specification of 31 in-lb (0.36 m-kg). The Kepnut provides a frame ground
connection that minimizes the possibility of loosening caused by rotation during installation and
maintenance activity. The type of prevention the Kepnut provides for the frame ground
connection is inherently provided by the terminal block for battery and battery return
connections.