Chapter 17
DLPs A1 to A99
Figure 17-2
Slide the air filter into the shelf assembly.
Step 4
Return to your originating procedure (NTP).
Step 5
DLP-A5 Mount the Shelf Assembly in a Rack (One Person)
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Step 1
Verify that the proper fuse and alarm panel has been installed in the top mounting space. If a fuse and
alarm panel has not been installed, you must install one according to the manufacturer's instructions.
•
•
March 2005
Installing the External Brackets
This task allows one person to mount the shelf assembly in a rack.
Pinned hex tool
Two set screws (48-1003-XX)
Eight pan-head Phillips mounting screws (48-1004-XX, 48-1007-XX)
#2 Phillips screwdriver
DLP-A3 Reverse the Mounting Bracket to Fit a 19-inch (482.6 mm) Rack,
page
DLP-A4 Install the External Brackets and Air Filter, page
applicable
As needed
Onsite
None
If you are installing the 15454-SA-ANSI or 15454-SA-HD shelf assembly, a 100-A fuse panel
(30-A fuse per shelf minimum) is required.
If you are installing the 15454-SA-NEBS3 shelf assembly, a standard 80-A fuse panel (20-A fuse
per shelf minimum) is required.
DLP-A5 Mount the Shelf Assembly in a Rack (One Person)
17-2, if applicable
Cisco ONS 15454 Procedure Guide, R5.0
17-4, if
17-5