DLP-A208 Change External Alarms Using the AIC-I Card
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
The procedure is the same if you are using the alarm expansion panel (AEP). In this case, the number of
Note
contacts that are shown on the screen is changed accordingly.
Confirm that external-device relays are wired to the ENVIR ALARMS IN backplane pins. See the
Step 1
"DLP-A19 Install Alarm Wires on the Backplane" task on page 17-22
Double-click the AIC-I card to display it in card view.
Step 2
Click the Provisioning > External Alarms tabs.
Step 3
Modify any of the following fields for each external device wired to the ONS 15454 backplane. For
Step 4
definitions of these fields, see the
Interface Controller-International" procedure on page
Cisco ONS 15454 Procedure Guide, R5.0
19-6
Installing Fiber-Optic Cables
SC cable connector
Front edge of card
This task changes external alarm settings on the Alarm Interface
Controller–International (AIC-I) card.
None
DLP-A60 Log into CTC, page 17-66
As needed
Onsite or remote
Provisioning or higher
Enabled
Alarm Type
Severity
Virtual Wire
Raised When
Description
Tx
Rx
"NTP-A258 Provision External Alarms and Controls on the Alarm
7-11.
Chapter 19
DLPs A200 to A299
for more information.