DLP-H251 Connect Office Power to the ONS 15310-MA SDH

Purpose
Tools/Equipment
Prerequisite Procedures Connect the office ground to the ONS 15310-MA SDH chassis. For detailed
Required/As Needed
Onsite/Remote
Security Level
If you encounter problems with the power supply, refer to the Cisco ONS 15310-MA SDH
Note
Troubleshooting Guide.
Connect the office power according to the fuse panel engineering specifications.
Step 1
Measure and cut the cables as needed to reach the ONS 15310-MA SDH from the fuse panel.
Step 2
Dress the power cabling according to local site practice.
Step 3
Remove or loosen the power terminal screws on the ONS 15310-MA SDH. To avoid confusion, label the
Step 4
cables connected to the BAT1/RET1 (A) power terminals as 1, and the cables connected to the
BAT2/RET2 (B) power terminals as 2.
Note
Note
Cisco ONS 15310-MA SDH Procedure Guide, Release 9.1 and Release 9.2
18-52
This task connects office power to the ONS 15310-MA SDH shelf.
#2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Wire wrapper
Wire cutters
Wire strippers
Fuse and alarm panel
Power cable (from fuse and alarm panel to assembly), #12 AWG, stranded
(41 strands, 0.010 in. [0.025 cm])
Listed pressure terminal connectors such as ring and fork types; 12 AWG,
stranded (41 strands, 0.010 in. [0.025 cm])
instructions on grounding, refer to the
(ESD) and Grounding
Required
Onsite
None
Use only pressure terminal connectors, including ring, fork, and dual-lug types, when
terminating the battery, battery return, and frame ground conductors.
The DC power Battery Return (BR) or positive terminal, must be grounded at the source end
(power feed or DC mains power end). The DC power BR input terminal of the ONS 15xxx
is not connected to the equipment frame (chassis).
Chapter 18
Cisco ONS Electrostatic Discharge
Guide.
DLPs H200 to H299
78-19416-01