Ntp-H63 Provision External Alarms And Controls - Cisco ONS 15310-MA SDH Procedure Manual

Hide thumbs Also See for ONS 15310-MA SDH:
Table of Contents

Advertisement

Before You Begin
Note
Complete the
Step 3
suppression and resume normal alarm reporting.
Stop. You have completed this procedure.

NTP-H63 Provision External Alarms and Controls

Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
External alarm physical connections are made using the ALARM port on the front of the
Note
ONS 15310-MA SDH. The alarms and controls are provisioned using the 15310E-CTX-K9 card view.
For information about the 15310E-CTX-K9 external alarms and controls, virtual wire, and orderwire,
refer to the Cisco ONS 15310-MA SDH Reference Manual.
Step 1
In the node view, double-click the active 15310E-CTX-K9 card. The card view appears.
If you are provisioning external alarms, click the Provisioning > External Alarms tabs
Step 2
(The view is similar for either platform.) If you are not provisioning external alarms, continue with
Step
To add User Defined Alarm Types, complete
Step 3
page
Cisco ONS 15310-MA SDH Procedure Guide, Release 9.1 and Release 9.2
8-8
Suppressing one or more alarms prevents them from appearing in Alarm or History windows or
in any other clients. The suppress command causes CTC to display them in the Conditions
window with their severity, their severity color code, and service-affecting status.
"DLP-H87 Discontinue Alarm Suppression" task on page 16-106
Use this procedure to create external (environmental) alarms and controls
on the ONS 15310-MA SDH.
None
DLP-H253 Install External Alarm Cables on the ONS 15310-MA SDH,
page 18-54
As needed
Onsite or remote
Provisioning or higher
7.
18-76. If you are not adding User Defined Alarm Types continue with
the"DLP-H277 Create User Defined Alarm Types" task on
Chapter 8
Manage Alarms
to discontinue alarm
(Figure
8-3).
Step 4
78-19416-01