Install the Cisco ONS 15310-MA SDH
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
Warning
installation. Install only in accordance with national and local wiring regulations. Statement 1045
Read the installation instructions before connecting the system to the power source. Statement 1004
Warning
Warning
This unit might have more than one power supply connection. All connections must be removed to
de-energize the unit. Statement 1028
Warning
This equipment must be grounded. Never defeat the ground conductor or operate equipment in the
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection
authority or an electrician if you are uncertain that suitable grounding is available. Statement 1024
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
When installing or replacing the unit, the ground connection must always be made first and
Warning
disconnected last. Statement 1046
Connect the unit only to DC power source that complies with the safety extra-low voltage (SELV)
Warning
requirements under IEC 60950-1 based safety standards. Statement 1033
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
Warning
Statement 1022
Warning
Use copper conductors only. Statement 1025
Note
The DC power Battery Return (BR), or positive terminal, must be grounded at the source end. The DC
power Battery Return input terminal is not connected to the equipment frame, so it is configured as DC-I
as per GR-1089 Issue 4 sec.9.8.3.
Always use the supplied ESD wristband when working with a powered ONS 15310-MA SDH. For
Caution
detailed instructions on how to wear the ESD wristband, refer to the
(ESD) and Grounding
Step 1
Verify that the proper fuse panel is installed. The fuses rating must not exceed 15A (Fast acting).