limit -15
huawei(config-if-smu-1)#power battery-test auto-test permit 180
huawei(config-if-smu-1)#display power battery-test info 1
huawei(config-if-smu-1)#power off load-off-state forbid load-off-voltage 44
battery-off-state permit battery-off-voltage 43
huawei(config-if-smu-1)#power temperature-off battery-off-state permit battery-off-
temperature 53
huawei(config-if-smu-1)#power environment temperature 68 -5 80 -20
This command is invalid unless in the contition of install the sensor, would
you continue? (y/n)[n]:y
huawei(config-if-smu-1)#power environment humidity 80 0 100 0
This command is invalid unless in the contition of install the sensor, would
you continue? (y/n)[n]:y
huawei(config-if-smu-1)#power module-num 3 1 2 3
huawei(config-if-smu-1)#power outside-digital 3 available-level low-level name SPD
digital-alarm 20
huawei(config-if-smu-1)#power outside-digital 5 available-level low-level name HEX
digital-alarm 13
huawei(config-if-smu-1)#power outside-digital 6 available-level low-level name MDF-
door digital-alarm 9
huawei(config-if-smu-1)#display power system parameter
huawei(config-if-smu-1)#display power environment parameter
huawei(config-if-smu-1)#display power alarm
huawei(config-if-smu-1)#quit
huawei(config)#save

1.3.16.9 Configuring the Power3000 Environment Monitoring Mode

This topic describes how to configure environment monitoring parameters by using the CLI.
Configuration Process
The monitoring parameters can be reported to the control system only when the data for the
Power3000 is configured correctly in the system.
Table 1-38
Table 1-38 Commands for configuring the Power3000
To...
Add an EMU
Query the configuration
parameters of the power system
Query the power environment
parameters
Configure the battery charging
parameters
Configure the battery
management parameters
Configure the upper/lower
temperature alarm limits or the
upper/lower temperature test
limits
Issue 01 (2014-04-30)
lists the commands used during the configuration.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Run the Command...
emu add
display power system parameter
display power environment parameter
power charge
power battery parameter
power battery temperature