Huawei SmartAX MA5603T Configuration Manual page 113

Access module
Hide thumbs Also See for SmartAX MA5603T:
Table of Contents

Advertisement

SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
Table 1-24 Data plan for configuring the H801VESC
Item
EMU
Digital
parameters
huawei(config)#emu add 2 H801VESC 0 25 H801VESC
huawei(config)#display emu 2
Issue 01 (2014-04-30)
Data
EMU ID: 2
Subnode ID: 25
Digital parameter ID: 0
Valid level of digital
parameter 0: low level
Name of digital
parameter 0:
Temperature
Digital parameter ID: 1
Valid level of digital
parameter 1: low level
Name of digital
parameter 1: Door
Digital parameter ID: 2
Valid level of digital
parameter 2: low level
Name of digital
parameter 2: Arrester
Digital parameter ID: 3
Valid level of digital
parameter 3: low level
Name of digital
parameter 3: Fan
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Remarks
The ID and subnode ID of the H801VESC cannot
conflict with those of the existing EMUs.
-
When the low level represents the valid level, the
MA5608T does not report an alarm in the case of
low level.
This digital parameter is set according to the actual
requirements. The monitoring digital parameter of
the temperature sensor is set to monitor the
temperature.
-
When the low level represents the valid level, the
MA5608T does not report an alarm in the case of
low level.
This digital parameter is set according to the actual
requirements. The monitoring digital parameter of
the door sensor is set to monitor the door status.
-
When the low level represents the valid level, the
MA5608T does not report an alarm in the case of
low level.
This digital parameter is set according to the actual
requirements. The monitoring digital parameter of
the lightning arrester status sensor is set to monitor
the arrester status.
-
hen the low level represents the valid level, the
MA5608T does not report an alarm in the case of
low level.
This digital parameter is set according to the actual
requirements. The monitoring digital parameter of
the fan status sensor is set to monitor the fan status.
NOTE
The enhanced heat dissipation module is an optional
module. The fan monitoring digital parameter is required
only when the enhanced heat dissipation module is
configured. Otherwise, the system will report an alarm.