The following considers the configuration in the F01S300 cabinet as an example to describe the
process of configuring the environment monitoring parameters of the EPS30-4815AF.
huawei(config)#emu add 0 POWER4830L 0 0 POWER4830L
huawei(config)#display emu 0
huawei(config)#interface emu 0
huawei(config-if-power4830l-0)#display power system parameter
huawei(config-if-power4830l-0)#display power environment parameter
huawei(config-if-power4830l-0)#power battery parameter 1 0.15 60 92
huawei(config-if-power4830l-0)#power battery-test auto-test permit 60
huawei(config-if-power4830l-0)#power temperature-off battery-off-state permit
battery-off-temperature 53
huawei(config-if-power4830l-0)#power environment temperature 68 -5 80 -20
huawei(config-if-power4830l-0)#power outside-digital 3 available-level low-level
name SPD digital-alarm 20
huawei(config-if-power4830l-0)#power outside-digital 4 available-level high-level
Issue 01 (2014-04-30)
Data Plan for the F01S300 Cabinet
Digital parameter ID: 4
This digital parameter is set according to the actual requirements. The
monitoring digital parameter of the smoke sensor is set here to monitor
whether there is smoke in the actual environment. When there is smoke,
the host reports an alarm.
Valid level of digital parameter 4: high level
When the high level represents the valid level, the host does not report
an alarm in the case of high level.
Digital parameter ID: 5
This digital parameter is set according to the actual requirements. The
monitoring digital parameter of the heat exchanger is set here to monitor
the status of the heat exchanger. When the heat exchanger is faulty, the
host reports an alarm.
Valid level of digital parameter 5: low level
When the low level represents the valid level, the host does not report
an alarm in the case of low level.
Digital parameter ID: 6
This digital parameter is set according to the actual requirements. The
digital monitoring parameter of the MDF door status sensor is set here
to monitor the MDF door status. When the door of the MDF
compartment is open, the host reports an alarm.
Valid level of digital parameter 6: low level
When the low level represents the valid level, the host does not report
an alarm in the case of low level.
The preceding data is configured according to the actual requirements. When the actually planned value
of a parameter is the same as the default value, it is not necessary to configure the parameter.
Huawei Proprietary and Confidential