Huawei SmartAX MA5603T Configuration Manual page 144

Access module
Hide thumbs Also See for SmartAX MA5603T:
Table of Contents

Advertisement

SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
Item
External extended digital
parameters
NOTE
Example
Assume that the F01D500 cabinet is configured with two 75 AH battery sets, the ETP4890 is
configured with 3 rectifier modules. To configure the environment monitoring parameters of the
ETP4890, do as follows:
huawei(config)#emu add 1 SMU 0 0 ETP4890
huawei(config)#display emu 1
huawei(config)#interface emu 1
huawei(config-if-smu-1)#display power system parameter
huawei(config-if-smu-1)#display power environment parameter
huawei(config-if-smu-1)#power battery parameter 0.15 60 1 150
huawei(config-if-smu-1)#power battery temperature 80 -20 80
huawei(config-if-smu-1)#power battery temperature alarm_upper-limit 50 alarm_lower-
Issue 01 (2014-04-30)
The preceding data is configured according to the actual requirements. When the actually planned value
of a parameter is the same as the default value, it is not necessary to configure the parameter.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Data Plan for the F01D500 Cabinet
Digital parameter ID: 3
Available-level: low level
Name: SPD
Digital-alarm-index: 20
NOTE
The monitoring digital parameter of the surge protector is set here to
monitor the surge protector. When the surge protector is faulty, the
device reports an alarm. The surge protector has the low level when
working properly and the device does not report an alarm.
Digital parameter ID: 5
Available-level: low level
Name: HEX
Digital-alarm-index: 13
NOTE
The monitoring digital parameter of the heat exchanger is set here to
monitor the status of the heat exchanger. When the heat exchanger is
faulty, the device reports an alarm. The heat exchanger has the low level
when working properly and the device does not report an alarm.
Digital parameter ID: 6
Available-level: low level
Name: MDF-door
Digital-alarm-index: 9
NOTE
The digital monitoring parameter of the MDF door status sensor is set
here to monitor the MDF door status. When the door of the MDF
compartment is open, the device reports an alarm. The MDF
compartment has the low level when its door is closed and the device
does not report an alarm.
1 Commissioning
119