Huawei SmartAX MA5603T Configuration Manual page 116

Access module
Hide thumbs Also See for SmartAX MA5603T:
Table of Contents

Advertisement

SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
To...
Configure the parameters for the
power rectifier module
Configure the battery high-
temperature power-off
parameters
Configure the environment
monitoring parameters
Configure the external extended
digital parameters
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. Query the alarms, and confirm that the door status alarm other than alarms for other
11. Save the data.
12. Close all doors of the cabinet. Then, query the alarm information again, and confirm that
Data Plan
In this topic, the application in the F01S300 cabinet is considered as an example.
provides the data plan for configuring the monitoring parameters of the EPS30-4815AF.
Issue 01 (2014-04-30)
Log in to the device through the maintenance terminal and add an EMU.
Query the status of the EPS30-4815AF.
Enter the environment monitoring configuration mode and query the default configuration.
Configure the battery management parameters.
Configure the battery discharging test parameters.
Configure the battery high-temperature power-off parameters.
Configure the environment parameters.
Configure the extended digital parameters.
Query the information about the configured parameters and environment parameters of the
power system.
monitoring parameters is generated. The door status sensors of the device compartment
and the temperature control compartment are in serial connection, and are monitored as a
variable.
there is no alarm for any monitoring parameter.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Run the Command...
power module-num
power temperature-off
power environment
power outside-digital
1 Commissioning
Table 1-27
91

Hide quick links: