Huawei SmartAX MA5603T Configuration Manual page 123

Access module
Hide thumbs Also See for SmartAX MA5603T:
Table of Contents

Advertisement

SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
6.
7.
8.
9.
10. Query the alarms, and confirm that the door status alarm other than alarms for other
11. Save the data.
12. Close all doors of the cabinet. Then, query the alarm information again, and confirm that
Data Plan
The data plan of the EPS75-4815AF in the N66 cabinet is the same as that in the F01D500
cabinets. In this topic, the application in the F01D500 cabinet is considered as an example.
1-30
Table 1-30 Data plan for configuring the monitoring parameters of the EPS75-4815AF
Item
EMU
Charging
parameters
of the battery
Issue 01 (2014-04-30)
Configure the battery high-temperature power-off parameters.
Configure the environment parameters.
Configure the extended digital parameters.
Query the information about the configured parameters and environment parameters of the
power system.
monitoring parameters is generated. The door status sensors of the device compartment
and the temperature control compartment are in serial connection, and are monitored as a
variable.
there is no alarm for any monitoring parameter.
provides the data plan for configuring the monitoring parameters of the EPS75-4815AF.
Data Plan for the F01D500
Cabinet
Type: POWER4875L
SN: 0
Subnode ID: 0
The subnode ID must be the same
as the subnode setting of the
corresponding DIP switches on the
EMU, but the subnode ID must be
different from IDs of the other
subnodes on the same bus.
Charging mode of the battery:
automatic
Equalized charging voltage of the
battery: 56.5 V
Float charging voltage of the
battery: 53.5 V
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Commissioning
Data Plan for the N66 Cabinet
Type: POWER4875L
SN: 0
Subnode ID: 0
The subnode ID must be the same as the
subnode setting of the corresponding
DIP switches on the EMU, but the
subnode ID must be different from IDs
of the other subnodes on the same bus.
Charging mode of the battery:
automatic
Equalized charging voltage of the
battery: 56.5 V
Float charging voltage of the battery:
53.5 V
Table
98