SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
Monitoring
Parameter
Displayed on
the Host
Environment
Tem
Smoke
Water
Procedure
Step 1 Log in to the device through the maintenance terminal and add an ETP4830 (SMU).
Run the emu add command to add the SMU.
Step 2 Check the default configurations of the power system.
Run the interface emu command to enter environment monitoring mode and then run the
display power system parameter and display power environment parameter commands to
query the default configurations.
Step 3 Configure parameters required for lead-acid batteries.
Run the power battery parameter command to configure parameters required for batteries,
including the management parameters, charging parameters, power-off parameters, and high-
temperature power-off parameters. You can use default values of these parameters for
configuration.
Step 4 Run the power battery temperature command to configure the upper/lower temperature test
limits, temperature compensation coefficient, and the upper/lower alarm temperature limits of
the battery set.
Step 5 (Optional) Configure discharging testing parameters.
l Run the power battery-test command to configure the discharging testing parameters,
including the automatic power-off test, scheduled automatic test, test interval for automatic
discharging, test time for delayed discharging, voltage at the stop of the test, number of
batteries in a battery set, time limit for the discharging test, time limit for simplified
discharging test, alarm thresholds for discharging efficiencies. You can use default values
of these parameters for configuration.
l Run the display power battery-test info command to query the discharge testing
information about the batteries.
Step 6 Run the power off command to configure the load power-off and battery set power-off voltage
parameters
Step 7 Run the power temperature-off command to configure the battery high-temperature power-off
parameters.
Step 8 Configure the environment monitoring parameters of the SMU system.
Run the power environment command to configure the upper alarm threshold and the upper
and lower test thresholds for the temperatures and humidity. After these parameters are set, the
Issue 01 (2014-04-30)
Device Port
VTEM2
SMOKE
WATER
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Application in the F01S300 Cabinet
Environment temperature sensor
Smoke sensor (optional configuration)
Water sensor (optional configuration)
1 Commissioning