huawei(config-if-power4875l-0)#power temperature-off battery-off-state permit
battery-off-temperature 53
huawei(config-if-power4875l-0)#power environment temperature 68 -5 80 -20
huawei(config-if-power4875l-0)#power outside-digital 3 available-level low-level
name SPD digital-alarm 20
huawei(config-if-power4875l-0)#power outside-digital 4 available-level high-level
name Smoke digital-alarm 15
huawei(config-if-power4875l-0)#power outside-digital 5 available-level low-level
name HEX digital-alarm 13
huawei(config-if-power4875l-0)#power outside-digital 6 available-level low-level
name MDF-door digital-alarm 9
huawei(config-if-power4875l-0)#display power system parameter
huawei(config-if-power4875l-0)#display power environment parameter
huawei(config-if-power4875l-0)#display power alarm
huawei(config-if-power4875l-0)#quit
huawei(config)#save
1.3.16.6 Configuring the Environment Monitoring Parameters of the GEPS4845
This topic describes how to configure the environment monitoring parameters of the GEPS4845
through the CLI.
Mapping Between Monitoring Parameters and Device Ports
Table 1-31
transfer box.
Table 1-31 Mapping between the monitoring parameters displayed on the host and the ports on
the sensor transfer box
Monitoring Parameter
Displayed on the Host
Digital 0
Digital 1
Digital 2
Digital 3
Digital 4
Digital 5
Digital 6
Door alarm
Issue 01 (2014-04-30)
describes the mapping between the monitoring parameters displayed on the sensor
Device Port
JTD1
JTD2
JTD3
JTD4
JTD5
JTD6
JTD7
JTM1
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Commissioning
Application in the F01D500
Cabinet
Not connected by default, used to
add a user-defined monitoring
digital parameter
Not connected by default, used to
add a user-defined monitoring
digital parameter
Not connected by default, used to
add a user-defined monitoring
digital parameter
surge protector (SPD)
Smoke sensor
Heat exchanger
Door status sensor of the MDF
compartment
Door status sensors of the device
compartment and heat exchanger
compartment
103