M800/M80/E80/C80 Series Alarm/Parameter Manual
2 Stop Codes (T)
2Stop Codes (T)
T01
Axis in motion
Details
Automatic start is not possible as one of the axes is moving.
Remedy
Try automatic start again after all axes have stopped.
T01
NC not ready
Details
Automatic start is not possible as the NC is not ready.
Remedy
Another alarm has occurred. Check the details and remedy.
T01
Reset signal ON
Details
Automatic start is not possible as the "reset" signal has been input.
Remedy
Turn OFF the "reset" signal.
Check for any failure of the reset switch which has caused the switch's continuous ON.
Correct the sequence program.
T01
Auto operation pause signal ON
Details
The feed hold switch on the machine operation panel is ON (valid).
Remedy
Correct the feed hold switch setting.
The feed hold switch is B contact switch.
Fix any broken wires in the feed hold signal line.
Correct the sequence program.
T01
H/W stroke end axis exists
Details
Automatic start is not possible as one of the axes is at the stroke end.
Remedy
Manually move any axis whose end is at the stroke end.
Check for any broken wires in the stroke end signal line.
Check for any failure in the stroke end limit switch.
T01
S/W stroke end axis exists
Details
Automatic start is not possible as one of the axes is at the stored stroke limit.
Remedy
Move the axis manually.
If the axis's end is not at the stroke end, check the parameters.
T01
No operation mode
Details
The operation mode has not been selected.
Remedy
Select automatic operation mode.
Check for any broken wires in the signal line for automatic operation mode (memory, tape, MDl).