M800/M80/E80/C80 Series Alarm/Parameter Manual
15 User Parameters
#9306
DEV2 CHR. LENGTH
[M8]
Select the length of the data bit.
Refer to "#9304 DEV2 PARITY CHECK".
0: 5 (bit)
1: 6
2: 7 (NC connection not supported)
3: 8
#9307
DEV2 TERMINATR TYP
[M8]
Select the code to terminate data reading.
0 and 3: EOR
1 and 2: EOB or EOR
* When M800W display side serial port is selected
0: No terminator
1: EOR
2: EOB
3: EOB or EOR
#9308
DEV2 HAND SHAKE
[M8]
Select the transmission control method.
No handshaking will be used when a value except 1 to 3 is set.
1: RTS/CTS method
2: No handshaking
3: DC code method
#9309
DEV2 DC CODE PRTY
[M8]
Select the DC code type when the DC code method is selected.
0: Not add parity to DC code (DC3 = 13H)
1: Add parity to DC code (DC3 = 93H)
#9311
DEV2 DC2/4 OUTPUT
[M8]
Select the DC code handling when outputting data to the output device.
DC2 / DC4
0: None / None
1: Yes / None
2: None / Yes
3: Yes / Yes
#9312
DEV2 CR OUTPUT
[M8]
Select whether to add the (CR) code just before the EOB (L/F) code during output.
0: Not add
1: Add
#9313
DEV2 EIA OUTPUT
[M8]
Select ISO or EIA code for data output.
In data input mode, the ISO and EIA codes are identified automatically.
0: ISO code output
1: EIA code output
IB-1501279-H
240