M800/M80/E80/C80 Series Alarm/Parameter Manual
16 Machine Parameters
#2582

BLAT_syn

[M8]
0: Separate backlash adjustment for master axis and slave axis each.
1: Backlash adjustment is applied only to the master axis. The master axis's backlash amount is applied to
the slave axis.
(Note 1) Set this parameter for the master axis.
(Note 2) In the case of synchronous control of speed/current command, set to "1".
#2584

VBL2 Vlimit

Specify the speed at which compensation scale is reset to 100%.
When set to "0", this parameter is disabled.
If a set speed is greater than "#2574 VBL2 VBound", the speed is clamped at "#2574 VBL2 VBound".
---Setting range---
0 to 1000000 (mm/min)
#2598
G0tL_2
Set a linear control time constant for rapid traverse acceleration/deceleration to be applied when the G0 time
constant switchover request signal is ON.
This time constant is enabled when LR (rapid traverse feed with linear acceleration/deceleration) or F (soft
acceleration/deceleration) is selected in "#2003 smgst (Acceleration and deceleration modes)".
If #2598 is 0, the time constant set in "#2004 G0tL (G0 time constant)" will be used.
---Setting range---
0 to 4000(ms)
#2599

G0t1_2

Set a primary-delay time constant for rapid traverse acceleration/deceleration to be applied when the G0 time
constant switchover request signal is ON.
This time constant is enabled when R1 (rapid traverse feed with primary delay) or R3 (exponential acceler-
ation and linear deceleration) is selected in "#2003 smgst (Acceleration and deceleration modes)".
If soft acceleration/deceleration is selected, the second-step time constant will be used.
If #2599 is set to 0, the time constant set in "#2005 G0t1 (G0 time constant (primary delay)/2nd-step time
constant for soft acceleration/deceleration)" will be used.
---Setting range---
0 to 5000(ms)
(PR)
#2614

JH_smgSel

Switch jog/handle time constants. Set per axis.
0: Disable
1: (Not used)
2: Enable for handle feed
#2616
JHtL
Set a linear control time constant for jog/handle feed acceleration/deceleration.
When set to "0", the time constant will be clamped at 1 [ms].
Speed
JHtL
---Setting range---
0 to 4000 (ms)
Synchronization setting for automatic backlash adjust-
ment
Variable backlash compensation 2: Speed to reset com-
pensation scale to 100%
G0 time constant 2 (linear)
G0 time constant 2 (primary delay)/2nd-step time con-
stant for soft acceleration/deceleration
Jog/handle acceleration/deceleration selection
Jog/handle time constant (linear)
Time
JHtL
497
IB-1501279-H