14 Multi CPU Errors (A) [C80]
A01
Remote A password setting error
Details
In the multiple CPU system, the module controlled by another CPU module is specified by the start I/O
number of the remote password setting.
Remedy
Check and correct the remote password setting.
A01
Module verification error
Details
The module information at power-on differs from the information of modules actually mounted.
The I/O module or intelligent function module is not mounted properly or was removed during operation.
Remedy
Check the detailed information (system configuration information) of the error by executing module diag-
nostics using the engineering tool, and check the module corresponding to the displayed number.
A01
Module verification error
Details
A CPU module, I/O module, or intelligent function module was mounted on the base unit during operation.
Remedy
Check the detailed information (system configuration information) of the error by executing module diag-
nostics using the engineering tool, and check the module corresponding to the displayed number.
Do not mount a CPU module, I/O module, nor intelligent function module during operation.
A01
Fuse blown error
Details
The output module with a blown fuse has been detected.
Remedy
Check the FUSE LED of each output module, and replace the one with the FUSE LED on.
Check the detailed information (system configuration information) of the error by executing module diag-
nostics using the engineering tool, and replace the module corresponding to the displayed number.
A01
Module major error
Details
In the multiple CPU system, the control CPU setting in the system parameters is different from that of other
numbered CPU modules.
An error has been detected in the I/O module or intelligent function module during the initial processing.
Remedy
Correct the system parameter settings for the CPU No.2 and later. The settings need to be the same be-
tween all the CPU modules.
Reset the CPU module, and run it again. If the same error code is displayed again, the possible cause is
a hardware failure of the error module. Please consult your local Mitsubishi representative.
A01
Module major error
Details
An error has been detected in the I/O module or intelligent function module during the END processing.
Remedy
The possible cause is a hardware failure of the error module. Please consult your local Mitsubishi repre-
sentative.
A01
Module major error
Details
An error has been detected in the I/O module or intelligent function module.
Remedy
The possible cause is a hardware failure of the error module. Please consult your local Mitsubishi repre-
sentative.