Connecting To Ethernet Module (Qna Series) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

5.4.10

Connecting to Ethernet module (QnA Series)

This section describes the settings of the GOT and Ethernet module (QnA Series) in the following case of the system
configuration.
■1. System configuration
*1
The Ethernet module is mounted on the base unit slot 0.
The Start I/O No. of the Ethernet module is set to "0".
■2. Switch settings of Ethernet module
Set the operation mode setting switch and exchange condition setting switch.
*1
The figure of AJ71QE71N3-T and A1SJ71QE71N3-T.
POINT
POINT
POINT
Ethernet module (QnA Series)
For details of the Ethernet module (QnA Series), refer to the following manual.
For QnA Ethernet Interface Module User's Manual
<Ethernet module> (The settings other than
the following are set to the default)
Network No.
PLC No.
IP address
Port No.
Communication format
AJ71QE71N3-T, AJ71QE71N-B5,
AJ71QE71N-B2, AJ71QE71N-T,
AJ71QE71N-B5T, AJ71QE71,
AJ71QE71-B5
*1
A
J71QE71N3-T
RUN
BUF1
BUF2
RDY
BUF3
BSY
BUF4
SW.ERR.
BUF5
COM.ERR.
BUF6
CPU R/W
BUF7
BUF8
TEST
TEST ERR.
MODE
C
(1)
0:ONLINE
1:OFFLINE
2:TEST1
3:TEST2
ON
4:TEST3
5:TEST4
SW1
SW2
SW3
(2)
SW4
SW5
SW6
SW7
SW8
10BASE-T
<GOT>(The settings other than
the following are set to the default)
Network No.
: 1
PLC No.
: 1
IP address
: 192.168.3.18
Port No.
: 5001
Communication format
: UDP(fixed)
*1
: 1
: 2
: 192.168.3.19
: 5001
: UDP(fixed)
A1SJ71QE71N3-T, A1SJ71QE71N-B5,
A1SJ71QE71N-B2, A1SJ71QE71N-T,
A1SJ71QE71N-B5T, A1SJ71QE71-B5,
A1SJ71QE71-B2
*1
A
1SJ71QE71N3-T
RUN
BUF1
RDY
BUF2
BSY
BUF3
SW.ERR.
BUF4
COM.ERR.
BUF5
TEST
BUF6
TEST ERR.
BUF7
CPU R/W
BUF8
MODE
0:ONLINE
C
1:OFFLINE
(1)
2:TEST1
3:TEST2
4:TEST3
5:TEST4
SW1
SW2
SW3
SW4
(2)
SW5
SW6
SW7
SW8
ON
10BASE-T
A1SJ71QE71N3-T
5.4 PLC Side Setting
5
5 - 73