(2) Setting method (Ethernet connection)
System configuration example 2: Ethernet connection
Station No. 3
Control system
(System A)
Connected module
Ethernet module of control system
Ethernet module of standby system
GOT connected to the Ethernet network
Step 1.
Set the screen switching device of the base screen.
Select [Common]
device GD100 as the base screen switching device.
Step 2.
Set the trigger action.
Make the setting so that the station number is switched when the faulty station information (GS231) from
the station monitoring specified by selecting [Common]
Condition 1 : GS231.b0 (while ON)
Operation
: GD100=2
Condition 1 : GS231.b1 (while ON)
Operation
: GD100=1
Step 3.
Set monitor screens.
For MELSECNET/H connection, MELSECNET/10 connection or Ethernet connection: (Common)
• Create a monitor screen with each object whose network setting is Station No. 1 on Screen No. 1 (1-1).
• Create a monitor screen with each object whose network setting is Station No. 2 on Screen No. 2 (1-2).
Ethernet
Network No. 1
GOT
Q25PRH
QJ71
E71
CPU
Station No. 1
[GOT Environmental Setting]
When b0 is ON, Station No. 1 is abnormal.
Screen No. is changed to 2.
When b1 is ON, Station No. 2 is abnormal.
Screen No. is changed to 1.
Standby system
Q25PRH
QJ71
(System B)
E71
CPU
Station No. 2
Network No.
1
[Screen Switching/Window], and set the internal
[trigger action] turns ON.
4.2 MELSEC Q Series
Station No.
4
1
2
3
4 - 85