12.4.11 Connecting to CC-Link module (A Series)

This section describes the settings of the GOT and CC-Link module (A Series) in the following case of system configuration.
■1. System configuration
*1
12 - 62
12.4 PLC Side Setting
POINT
POINT
POINT
CC-Link module (A Series)
For details of the CC-Link module (A Series), refer to the following manual.
Control & Communication Link System Master/Local Module Type AJ61BT11/
A1SJ61BT11 User's Manual
<CC-Link module>
*1
(Use the default value for settings other than the following.)
Station type
: Master station
: Station No.0
Station No.
Mode setting
: Remote net mode
All connect count
: 1
Transmission speed : 156kbps
Module mode
: Intelligent mode
The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
<GOT>
(Use the default value for settings other
than the following.)
: Intelligent device
Station type
station
Station No.
: Station No.1
Number of station occupied : Exclusive station 1
Transmission
: 156kbps
speed