12.5 Precautions

■1. Using cyclic transmission
(1) I/O signal for master station
Do not turn on the reserved output signals in the output signals (remote output: RY) to the GOT from the master
station.
When the reserved output signal is turned on, the PLC system may be malfunctioned.
For the assignment of I/O signals in the GOT, refer to the following manual.
MODEL GT15-J61BT13 CC-Link communication unit User's Manual
GT15 CC-Link communication unit User's Manual
(2) Access range that can be monitored
The monitoring range of remote I/O (RX and RY) and that of the remote registers (RWr and RWw) vary according to
the mode in the master station of the CC-Link system.
Mode of master station
Remote net mode
Remote net ver.1 mode
Remote net ver.2 mode
Remote net additional mode
*1
Monitoring is applicable only when MODEL GT15-J61BT13 CC-Link communication unit is used.
(3) When GOT malfunctions, the cyclic output status remains the same as before becoming faulty.
■2. For transient transmission
(1) CC-Link module of target station
Mount the CC-Link module of function version B or later and software version J or later to the PLC CPU when
performing the following CC-Link modules and transient transmission.
Only cyclic transmission can be communicated with the CC-Link module of function version A or before and software
version I or before.
• AJ61BT11
• A1SJ61BT11
• AJ61QBT11
• A1SJ61QBT11
(2) Access range that can be monitored
The GOT can access to the PLC CPU mounting the master and local station of the CC-Link System.
It cannot access another network via the CC-Link module.
■3. GOT startup in the CC-Link connection (intelligent device station)
For CC-Link connection (intelligent device station), the data link is started approximately 10 seconds after the GOT
startup.
■4. When a network error occurs in the system alarm
In the CC-Link connection (intelligent device station), when a network error occurs in the system alarm, the system
alarm display cannot be canceled even though the causes are removed.
To cancel the system alarm display, restart the GOT.
■5. Connection in the multiple CPU system
When the GOT is connected to multiple CPU system, the following time is taken until when the PLC runs.
MELSEC iQ-R series, motion controller CPU (MELSEC iQ-R series), QCPU (Q mode), motion controller CPU (Q
series): 10 seconds or more
MELDAS C70: 18 seconds or more
When the GOT starts before the PLC runs, a system alarm occurs.Adjust the opening screen time in the GOT setup so
that no system alarm occurs.
GT Designer3 (GOT2000) Screen Design Manual
Applicable of monitoring
Data for each station compatible with
CC-Link ver.1
: Applicable
Data for each station compatible with
CC-Link ver.2
-
-
*1
*1
: N/A(All "0") -: N/A of system configuration
12.5 Precautions
12
12 - 81