Plc Side Setting; Connecting To Ethernet Interface Module (F3Le01-5T, F3Le11-0T) - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

Ethernet setting
Item
Description
The host is displayed.(The host is
Host
indicated with an asterisk (*).)
Set the network No. of the
N/W No.
connected Ethernet module.
(Default: blank)
Set the station No. of the
*3
connected Ethernet module.
PLC No.
(Default: blank)
Type
YOKOGAWA (fixed)
Set the IP address of the
*1
connected Ethernet module.
IP address
(Default: blank)
Set the port No. of the connected
*2
Ethernet module.
Port No.
(Default: 12289)
Communication
Select a communication protocol.
*1
(Default: UDP)
format
*1
Set the same IP address and communication format as
those of the PLC side.
*2
Set the port No. of the host link service used on the PLC
side.
*3
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
 Communication detail settings
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GT
User's Manual
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
7.3.3
POINT
POINT
POINT
YOKOGAWA PLC
For details of YOKOGAWA PLCs, refer to the following
manuals.
Set value
Ethernet interface module
Built-in Ethernet interface
1 to 239
1 to 64
7.3.4
YOKOGAWA
(fixed)
PLC side IP
address
Switch settings of Ethernet Interface Module
Set the switches accordingly.
12289, 12291
POINT
POINT
POINT
UDP, TCP
Switch setting
Set the switches before mounting the Ethernet
Interface Module on the base unit.
(1) IP address switch
Set the IP address with eight Hex rotary switches on
the side of the base unit.
Hexadecimal
Decimal
7. CONNECTION TO YOKOGAWA PLC

PLC side setting

YOKOGAWA PLC user's Manual
Model name
F3LE01-5T
F3LE11-0T
F3LE12-0T
F3SP66
F3SP67
F3SP71-4N
Connecting to Ethernet
Interface Module (F3LE01-5T,
F3LE11-0T)
F3LE01-5T
Condition setting
switch
IP address switch
Right side view without the cover
C0
A8
192
168
7.3 Ethernet Connection
1
2
Refer to
7.3.4
3
7.3.5
7.3.6
4
5
F3LE11-0T
6
7
8
FA
D2
250
210
7 - 19