■5. Connection to Q170MCPU or Q170MSCPU(-S1)
Set [CPU No.] to "2" in the device setting to monitor the device of the Motion CPU area (CPU No.2).
When the CPU No. is set to "0" or "1", the device on the PLC CPU area (CPU No.1) is monitored.
When the CPU No. is set to the number other than "0" to "2", a communication error occurs and the monitoring cannot
be executed.
For setting the CPU No., refer to the following manual.
GT Designer3 (GOT2000) Screen Design Manual
Example) Setting dialog box of the bit device
■6. Connection to MELSEC iQ-F Series
Module parameter settings as a default value (MELSOFT Connection).
If it sets up other than a default value, it becomes impossible to communicate with GOT.
(1) Module parameter setting
(When using FX5-485-BD)
■7. Connection with the motion controller A series
When the following motion controller is connected, "LINK UNIT ERROR(42)" may occur in SCPU (CPU for PLC
control) depending on the contents of the display screen. In this case, reduce the object points of the screen which are
displayed on one screen. 128 points or less is recommended. More reduction may be needed depending on the project
of the GOT.
Motion controller (A series): A171SHCPU, A171SHCPUN, A172SHCPU, A172SHCPU
POINT
POINT
POINT
MELSEC iQ-F Series communication settings
For details of MELSEC iQ-F Series communication settings, refer to the following manual.
MELSEC iQ-F Series User's Manual
POINT
POINT
POINT
When changing the module parameter
After writing module parameters to the PLC CPU, turn the PLC CPU OFF then back ON again, or
reset the PLC CPU.
6 - 57
6.6 Precautions