9.4

PLC side setting when connecting to MELSECNET/H

This section describes the settings of the GOT and MELSECNET/H network module in the case of system configuration
shown as 9.4.1.
When connecting the MELSECNET/H network module to the MELSECNET/H network system, specify the MELSECNET/H
Mode or the MELSECNET/H Extended Mode as a network type.
9.4.1
System configuration
*1
*2
9 - 18
9.4 PLC side setting when connecting to MELSECNET/H
POINT
POINT
POINT
MELSECNET/H network module
For details of the MELSECNET/H network module, refer to the following manual.
Q corresponding MELSECNET/H Network System Reference Manual (PLC to PLC
network)
MELSECNET/H (PLC to PLC network)
The MELSECNET/H network module is mounted at slot 0 of the base unit.
The start I/O No. of the MELSECNET/H network module is set at "0".
The network type must be set according to the number of assignment of send points for each station.
When the number of assignment is 2000 bytes or less:
MELSECNET/H mode
When the number of assignment is 2000 bytes or more:
MELSECNET/H Extended Mode
POINT
POINT
POINT
When connecting to Q170MCPU or Q170MSCPU(-S1)
When connected to Q170MCPU or Q170MSCPU(-S1), the start I/O No. of the MELSECNET/H
network module is set to "70".
<GOT>
(Use the default value for settings other
than the following.)
<MELSECNET/H network module> *
1
(Use the default value for settings other than the following.)
Station No.
: 1
Mode
: Online (10Mbps)
Network type
: MNET/H mode (Control station)
Network No.
: 1
Total stations
: 2
Network range assignment *
2
:
LB0000
to LB00FF
H
LW0000
to LW00FF
H
LB0100
to LB01FF
H
H
LW0100
to LW01FF
H
H
H
H