Connecting To Ethernet Module (Qna Series) - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

(1) Controller setting
Item
GOT NET No.
GOT PLC No.
GOT IP Address
GOT Port No. (Communication)
GOT Port No.
(Ethernet Download)
Default Gateway
Subnet Mask
Retry
Startup Time
Timeout Time
Delay Time
(2) Ethernet setting
Item
Host
N/W No.
PLC No.
Ethernet setting
Type
No.1
IP address
Port No.
Communication
*1
Set the same value as that of GOT N/W No.
*2
Set a value different from that of the GOT PLC No. and the
PLC No. of other PLCs on the same network.
Checking communication state of C
Controller module (Q Series)
(1) When using the Command Prompt of Windows
Execute a Ping command at the Command Prompt of
Windows
.
(a) When normal communication
C:\>Ping 192.168.3.1
Reply from 192.168.3.1: bytes=32 time
<10ms TTL=32
(b) When abnormal communication
C:\>Ping 192.168.3.1
Request timed out.
(2) When abnormal communication
At abnormal communication, check the followings and
execute the Ping command again.
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• The IP address of C Controller module (Q Series)
specified in the ping command
Set value (Use default value)
1
1
192.168.3.18
5001
5014
0.0.0.0
255.255.255.0
3times
3sec
3sec
0ms
Set value
*
-
*1
*1
1
1
*2
*2
2
3
QnD(H)CCPU
QnD(H)CCPU
192.168.3.1
192.168.3.2
5006 (fixed)
5006 (fixed)
UDP (fixed)
UDP (fixed)
.
8.4.9
Connecting to Ethernet
module (QnA Series)
This section describes the settings of the GOT and
Ethernet module (QnA Series) in the following case of the
system configuration.
POINT
POINT
POINT
Ethernet module (QnA Series)
For details of the Ethernet module (QnA Series), refer
to the following manual.
For QnA Ethernet Interface Module User's
Manual
System configuration
[Controller Setting] and [Ethernet] of GT
Designer3
<GOT>(The settings other than
the following are set to the default)
Network No.
PLC No.
IP address
Port No.
Communication format
<Ethernet module> (The settings other than
the following are set to the default)
Network No.
PLC No.
IP address
Port No.
Communication format
■ Switch settings of Ethernet module
■ [Network parameter] of GX Developer
*1
The Ethernet module is mounted on the base unit slot 0.
The Start I/O No. of the Ethernet module is set to "0".
8. ETHERNET CONNECTION
8.4 PLC Side Setting
: 1
: 1
: 192.168.0.18
: 5001
: UDP(fixed)
*1
: 1
: 2
: 192.168.0.19
: 5001
: UDP(fixed)
8 - 41
1
2
3
4
5
6
7
8