Mitsubishi Electric GOT2000 Series Connection Manual page 695

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) Station information setting
Station type
*2
Expanded cyclic setting
*2
Exclusive station count
Remote station points
Reserve/invalid station select
Intelligent buffer select (word)
*1
When the [Mode] of the CC-Link module is set at [Remote net - (Ver. 2 mode)], [Remote station points] can be set.
[Remote station points] is a setting for the remote I/O station.
The default value (32 points) must be used on the GOT.
*2
Set the same setting as that of the GOT.
■3. [Controller Setting] of GT Designer3
Station No.
Transmission Rate
Mode
Expanded Cyclic
Number of stations occupied
Input for Error Station
Retry
Timeout Time
Delay Time
Transmission method
*1
Item
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU, operate the PLC CPU either turning OFF
and then ON or resetting.
Item
POINT
POINT
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT Designer3, refer to the following.
12.3.1 Setting communication interface (Controller Setting)
Set value
Ver.2 intelligent device station (fixed)
Single
Exclusive station 1
32 points (fixed)
No setting
(Use default value)
: Necessary
: As necessary
Set value
1: Station No.1
0: Online 156kbps
Ver.2: Remote net (Ver.2 mode)
Single
1 Station
0: Clear
3times (Use default value)
3sec (Use default value)
0ms (Use default value)
MELSEC (compatible)
12.4 PLC Side Setting
Setting necessity at GOT
connection
: Not necessary
12
12 - 53