5.4.2
Connecting to MELSEC iQ-R Series built-in Ethernet port CPU
(multiple connection)
This section describes the settings of the GOT and Built-in Ethernet port CPU in the following case of system configuration.
■1. GOT Side Communication format is UDP
(1) System configuration
(MELSEC iQ-R Series)
*1
(2) [Module parameter] of GX Works3
(a)
Built-in Ethernet port
(For MELSEC iQ-R Series)
IP Address
Subnet Mask
Default Gateway
5 - 34
5.4 PLC Side Setting
POINT
POINT
POINT
Built-in Ethernet port CPU
For details of Built-in Ethernet port CPU, refer to the following manual.
➠
Manuals of MELSEC iQ-R Series
Manuals of MELSEC iQ-F Series
These setting items do not exist at the PLC side. However, the virtual values must be set on the GOT side.
➠
(3) [Controller Setting] and [Ethernet] of GT Designer3
Item
<GOT>
(Use the default value for settings
other than the following.)
Network No.
PLC No.
IP address
Port No.
Communication format :UDP (fixed)
<Built-in Ethernet port CPU>
1
(Use the default value for settings
other than the following.)
Network No.
:1 (virtual)
PLC No.
:2 (virtual)
IP address
:192.168.3.1
Port No.
:5006 (fixed)
Communication format :UDP (fixed)
<Built-in Ethernet port CPU>
2
(Use the default value for settings
other than the following.)
Network No.
:1 (virtual)
*1
PLC No.
:3 (virtual)
*1
IP address
:192.168.3.2
Port No.
:5006 (fixed)
Communication format :UDP (fixed)
Set value
192.168.3.1
:1
:1
:192.168.3.18
:5001
*1
*1
-
-
Setting necessity at GOT