17.6 Device Range that Can Be Set
For details of the device range that can be used on the GOT, refer to the following.
➠
17.7 Precautions
17.7.1
Direct connection to CPU
■1. Version of CNC
For MELDAS C6/C64, use NC system software version D0 or later.
17.7.2
MELSECNET/10 connection
■1. Network configuration
Use the MELSECNET/10 mode of MELSECNET/H (PLC to PLC network) or MELSECNET/10 (PLC to PLC network) to
configure a network including the GOT.
(1) The following networks including the GOT cannot be configured.
• MELSECNET/10 (Remote I/O network)
• MELSECNET/H (Remote I/O network)
(2) When configuring the network (MELSECNET/H (PLC to PLC network) including the GOT, refer to
the following.
➠
■2. Monitoring range
Only CNC of the same networks No. can be monitored in GOT.
For details, refer to the following manual.
➠
■3. Starting GOT with CNC connection (MELSECNET/10 connection)
With the CNC connection (MESLSECNET/10 connection), the data link starts approximately 10 seconds after the GOT
starts.
■4. When a network error occurs in the system alarm
When a system alarm regarding a network error occurs with the CNC connection (MELSECNET/10 connection), the
system alarm is kept displaying on the GOT even though the error factor is removed.
To cancel the system alarm display, restart the GOT.
■5. Version of CNC
For MELDAS C6/C64, use NC system software version E0 or later.
17 - 24
17.6 Device Range that Can Be Set
2.5 MELSEC-QnA, MELDAS C6 *
9. MELSECNET/H CONNECTION (PLC TO PLC NETWORK), MELSECNET/10 CONNECTION
(PLC TO PLC NETWORK)
3.1 Access Range for Monitoring Stations on Network Systems