Advertisement

PLC
Computer link
Model name
*1
module
AJ71UC24
MELSEC-QnA
(QnACPU)
AJ71UC24
*1
For the system configuration on the computer link module side, refer to the following manual.
Computer Link Module (Com. link func./Print. func.) User's Manual
When connecting to a computer link module, set the communication driver to [AJ71C24/UC24].
*2
For details of the GOT multi-drop connection, refer to the following.
19. GOT MULTI-DROP CONNECTION
*3
When a GT10-C02H-6PT9P unit of the sub version A or B is used, do not ground the case of the D-sub (9-pin) connector.
*4
GT25-W, GT2505-V does not support the option device.
Connection cable
Communication
Cable model
type
GT09-C30R2-25P(3m)
or
RS-232 connection
diagram 2)
RS-232
RS-232 connection
diagram 4)
GT09-C30R4-6C(3m)
GT09-C100R4-6C(10m)
GT09-C200R4-6C(20m)
GT09-C300R4-6C(30m)
or
RS-422 connection
RS-422
diagram 1)
RS-422 connection
diagram 2)
GOT
Max.
*4
Option device
distance
- (Built into GOT)
GT15-RS2-9P
15m
GT10-C02H-
*3
6PT9P
*2
GT01-RS4-M
15m
- (Built into GOT)
- (Built into GOT)
GT15-RS4-9S
500m
GT10-C02H-9SC
*2
GT01-RS4-M
500m
- (Built into GOT)
7.2 System Configuration
Number of
connectable
Model
equipment
-
1 GOT for 1
computer link
module
-
7 - 15
7