Mitsubishi Electric GOT2000 Series Connection Manual page 716

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(c)
Buffer memory settings used in the present example
Buffer memory address
*1
12 - 74
12.4 PLC Side Setting
Decimal (Hex)
0(0H)
1(1H)
2(2H)
3(3H)
6(6H)
12(CH)
6(DH)
32(20H)
33(21H)
Details for the station data are shown below.
For 1) and 2) and 3), set the same station No. and number of station occupied and expanded cyclic as those of the GOT.
b15
to
b12
b11
3)
1) Station No. (Set the same station No. as that of the GOT.)
01H to 10H: Station No.1 to Station No.16
2) Number of stations occupied (Set the same setting of the number of station occupied as that of the GOT.)
1H: Exclusive station 1
2H: Exclusive station 2
3H: Exclusive station 3
4H: Exclusive station 4
3) Station type
2H: Ver.1 compatible intelligent device station
6H: Ver.2 compatible single intelligent device station
9H: Ver.2 compatible double intelligent device station
CH: Ver.2 compatible quadruple intelligent device station
FH: Ver.2 compatible octuple intelligent device station
Item
Mode
Number of connected modules
Retry Count
Automatic Reconnection Station Count
PLC Down Select
Data Link Disorder Station Setting
Case of CPU STOP Setting
*1
Station information (1st unit)
*1
Station information (2nd unit)
to
b8
b7
to
2)
1)
Set value
2 (Remote net (Ver.2 mode))
2 (2module)
7 (7times)
2 (2module)
0 (stop)
1 (Clear)
0 (Refresh)
2301H
C104H
b0