Melsec Redundant Setting - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

4.3

MELSEC Redundant Setting

The following explains the setting for automatically change the monitoring target of the GOT when monitoring a RCPU
redundant system, QCPU redundant system.
Step 1.
Select [Common]
Step 2.
The setting dialog box appears. Make the settings with reference to the following explanation.
Step 3.
Make the settings for the MELSEC redundant setting.
In the MELSEC Redundant Setting dialog box, settings can be made for each channel of the controller.
(Example: Ethernet connection (Station No. 5), redundant CPU pair No. 1 and No. 2, redundant CPU station No. 1 to 4)
Item
CH1 to CH4
Follow the redundant
system via a serial
interface
NW No.
*1
Pair No.
Station
No.
New
Duplicate
Delete
Delete All
Copy All
Paste All
*1
For details of *1, refer to the explanation below.
POINT
POINT
POINT
Before making the MELSEC redundant setting
In the MELSEC redundant setting, do not set stations other than redundant CPUs.
[Controller Setting]
Select a tab of the CH No. for the MELSEC redundant setting.
Select this item to monitor the control system as a host station at serial connection.
Set the network No. (1 to 225) for each of pair numbers (1 to 64).
Upper row: Setting for the first redundant CPU.
Lower row: Setting for the second redundant CPU.
(The same value as the value set for the first redundant CPU is displayed)
Set the station No. (1 to 63) of the redundant CPU for each of pair numbers (1 to 64).
Upper row: Setting for the first redundant CPU.
Lower row: Setting for the second redundant CPU.
(The value of "Setting for the first redundant CPU" + 1 is displayed)
Create a new pair No.
Copies one setting of the selected pair number to append it at the last line.
Deletes one setting of the selected pair.
After deletion, the succeeding pair numbers are renumbered to fill the deleted pair number.
Deletes the setting of all pair numbers.
Copies the MELSEC redundant setting on the selected CH No. tab.
Pastes the copied MELSEC redundant setting in the selected CH No. tab.
[MELSEC Redundant] from the menu.
Contents
4.3 MELSEC Redundant Setting