Mitsubishi Electric GOT2000 Series Connection Manual page 257

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Step 6.
Change the station number switching device value in the script.
By selecting [Common]
SM1515 status of the current monitor station, and if it is OFF (standby system), changes the station
number switching device value.
Set the trigger type of the script as [Ordinary] or [Sampling(about 3s)].
• Screen script for Ethernet connection:
// If the host station is not a control station, the station number is switched to that of the other station.
if([b:SM1515]==OFF){
i
[ ( f
: w
G
D
1
0
0
= ]
=
0
[w:GD100]=0x0102;
e }
s l
{ e
[w:GD100]=0x0101;
}
}
For the Ethernet connection, create a script so that the network No. and station number are set to the
station switching device.
For Network No. 1 and Station No. 2, create "[w:GD100]=0x0102".
Set the created script for each screen on the Screen tab.
[Script]
[Script], create a script for each monitor screen that checks the
x
0
1
0
1
{ )
/ /
t S
t a
o i
n
N
. o
1
o t
2
/ /
t S
t a
o i
n
N
. o
2
o t
1