Chapter 1
Install Hardware
This procedure explains how to install the screw-lock power connector. To install the terminal-lug power
Note
connector also included with the ONS 15327, see the
15327 Shelf (Terminal-Lug Power Connector)" procedure on page
If you encounter problems with the power supply, refer to the Cisco ONS 15327 Troubleshooting Guide.
Note
Connect the office power according to the fuse panel engineering specifications.
Step 1
Measure and cut the cables as needed to reach the ONS 15327 from the fuse panel.
Step 2
Step 3
Dress the power according to local site practice.
When installing the ONS 15327, the ground connection must always be made first and disconnected
Warning
last.
Strip .22 inches of insulation from all power cables that you connect to the ONS 15327 power
Step 4
connectors.
Do not expose more than .22 inches of bare wire on power cables.
Warning
If the power connector is already installed, remove it from the MIC by grasping it with your fingers and
Step 5
gently pulling it. If you cannot remove it easily, you can use a pair of needle nose pliers and grab it by
the center of the channel.
March 2003
Figure 1-4
shows the MIC power connector being removed.
NTP-B6 Install the Power and Ground
"NTP-B222 Connect Office Power to the ONS
D-4.
Cisco ONS 15327 Procedure Guide, R4.0