5 Troubleshooting by event log
5.10 11 xxxx
Continued
The gun is not force calibrated and/or a template servogun
configuration file is loaded. If using a template file an initial
force table can be set by running the service routine
'ManualForceCalib' or 'ManualServiceCalib'.
Force difference between configured max gun force and last
entry in force calibration table is too big: arg arg.
Current gun: arg.
Consequences
Execution is stopped.
Recommended actions
Set an initial force table or perform a force calibration of the
gun with the service routine 'ManualForceCalib'.
110700, No weld internal.
Description
Task:arg
arg
Weld signal switched off at programming terminal.
Recommended actions
Check programming unit setting Operating mode for Weld
on/off, int.(S)/Weld/No weld (T).
110701, No weld external.
Description
Task:arg
arg
External weld signal was deactivated.
Recommended actions
Check signal at weld external input.
110702, The weld sequence is inhibited, weld
schedule stopped.
Description
Task:arg
arg
The started program was inhibited for the sequence/schedule
Recommended actions
Enable program at the programming terminal at Operation -
Modify - Programming - Sequence Setup Inhibit Sequence
(S)/Start- Inhibit (T) for all programs or Inhibit Sequence
(P)/Start-Inhibit (P) for one program - check program selection,
select proper program.
Continues on next page
488
110703, No valid weld program, no schedule
programmed.
Description
Task:arg
arg
wrong program selected - invalid spot selection - invalid
parameters in started program
Recommended actions
Check program selection - check spot selection - check value
range of the following parameters: power unit number,
electrode/stepper number, program number.
110704, The battery backup is low.
Description
Task:arg
arg
The buffer battery voltage has dropped
Recommended actions
Replace the backup battery in the weldtimer.
110705, Memory has been deleted.
Description
Task:arg
arg
All data of this weld timer has been deleted: - new timer
firmware was copied to system - battery is low or defective.
Recommended actions
Copy data (Operation - Services - Restore/Download) if the
error occurs repeatedly, replace timer.
110706, There is a hardware fault.
Description
Task:arg
arg
Defective module. When booting, a module is detected which
does not match the firmware: - a firmware was introduced into
the weld timer which is not permitted for the existing hardware.
Recommended actions
Replace module or timer - replace module - load proper firmware
to the timer.
110707, External temperature too high.
Description
Task:arg
© Copyright 2005-2018 ABB. All rights reserved.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA