71296, Invalid output size
Description
On DeviceNet I/O device arg the connection 2 output size does
not match the I/O device.
Recommended actions
Change size in I/O configuration. Check module.
71297, Invalid connection type
Description
The DeviceNet I/O device arg does not support arg connection.
Recommended actions
Change connection type in I/O configuration. Use DN_Generic
device template.
71298, Duplicated address
Description
The address arg for the DeviceNet master on network DeviceNet
is occupied by the I/O device arg on the network.
Recommended actions
Change master address in I/O configuration. Disconnect I/O
device occupying the address from the network. Restart the
controller.
71299, No power on DeviceNet network
Description
The 24 V power supply from the DeviceNet power supply is
missing.
Consequences
No communication on the DeviceNet network is possible.
Probable causes
The power supply unit, cabling, input voltage to the power
supply or the output load may cause the power loss. See the
Trouble Shooting Manual and Circuit Diagram!
Recommended actions
Check all cabling to the power supply unit. Measure the output
and input voltage levels. Replace the faulty I/O device if
required.
71300, DeviceNet network communication
warning
Description
A minor number of communication errors occurred on the
DeviceNet network.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA
Consequences
Normal operation will be maintained, even on the DeviceNet.
Probable causes
The fault may be caused by interference, power supply units
and cables, or communication cables.
Recommended actions
Make sure any terminating resistors are correctly connected.
Make sure all communication cables and connectors are
working correctly and of the recommended type. Check network
topology and cable length. Make sure the DeviceNet Power
Supply unit is working correctly. Replace any faulty unit.
71301, Bus off, DeviceNet network
communication failure
Description
A major number of communication errors occurred on DeviceNet
network.
Consequences
All communication on the DeviceNet Bus has stopped.
Probable causes
The fault may be caused by interference, power supply units
and cables, or communication cables.
Recommended actions
Make sure the DeviceNet power supply unit is working correctly.
Replace any faulty I/O device. Make sure any terminating
resistors are correctly connected. Make sure all communication
cables and connectors are working correctly and of the
recommended type. Check network topology and cable length.
Restart the controller.
71302, No DeviceNet option has been installed
Description
A DeviceNet master/slave board has been fitted, but no
DeviceNet option has been installed.
Consequences
No communication on the DeviceNet is possible. There may be
consequential errors from configuring DeviceNet when no such
option has been installed.
Probable causes
An attempt may have been made to add the DeviceNet
functionality, without installing the option correctly.
Recommended actions
If the DeviceNet option is required: configure a new system
with this option, and install the system. If the DeviceNet option