5 Troubleshooting by event log
5.9 9 xxxx
Continued
with different IP Address and/or Safety Network Number (SNN)
already owns inputs of the CIP Safety Adapter. The IP Address
and SNN of the current owner are written to Non Volatile
Memory of the CIP Safety Adapter.
Consequences
An external CIP Safety Scanner will not be able to connect and
write signals to the CIP Safety Adapter of the Robot Controller.
Probable causes
The IP Address and/or SNN of the external CIP Safety Scanner
has changed. The inputs of this CIP Safety Adapter is already
owned by another external CIP Safety Scanner.
Recommended actions
Verify that the IP Address and SNN of the external CIP Safety
Scanner is as intended. Reset CIP Safety to clear the ownership
from Non Volatile Memory of the CIP Safety Adapter.
90780, Two-channel fault in Safety Controller
Description
Two-Channel fault for Safety Controller GPIO input arg: arg !=
arg.
Consequences
The system will stop all robot movements.
Probable causes
Cable fault. Signaling error.
Recommended actions
Check cables to the Safety Controller. Restart the robot
controller.
90781, Safe Local I/O GPIO input is unstable
Description
arg SNC: GPIO input arg is unstable.
This is a warning only.
Probable causes
Cable fault. Signaling error.
Recommended actions
Check cables to the Safety Controller. Verify that the indicated
signal to the Safety Controller is stable.
90790, arg setup failed
Description
The arg was unable to setup properly.
Consequences
arg is not running.
Continues on next page
444
Probable causes
No communication with the PROFIsafe host. Bad parameter
values.
Recommended actions
Check parameters and connection to the PROFIsafe host. Try
again.
90791, arg start failed
Description
The arg was unable to start.
Consequences
arg is not running.
Probable causes
No communication with the PROFIsafe host. Bad parameter
values.
Recommended actions
Check parameters and connection to the the PROFIsafe host.
Try again.
90792, arg fail-safe activated
Description
The arg has activated fail-safe values.
Probable causes
Lost communication with the PROFIsafe host.
Recommended actions
Check connection to the PROFIsafe host.
90793, arg Operator Acknowledge
Description
The arg is in Operator Acknowledge state.
The PROFIsafe host is waiting for operator acknowledgement.
Consequences
arg is sending fail-safe values.
Probable causes
Communication with the the PROFIsafe host has been
established.
Recommended actions
Activate the Operator Acknowledge signal for about 1 second.
90794, arg parameter mismatch
Description
The arg F-Parameters do not match F-Parameters from the
PROFIsafe host.
© Copyright 2005-2018 ABB. All rights reserved.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA