5 Troubleshooting by event log
5.9 9 xxxx
Continued
Consequences
The system will stop all robot movements.
Probable causes
The safety configuration has not been created using
RobotStudio.
Recommended actions
Update the safety configuration.
90612, Device attribute insize is invalid
Description
Device arg attribute insize is empty or not a number.
Consequences
The system will stop all robot movements.
Probable causes
The safety configuration has not been created using
RobotStudio.
Recommended actions
Update the safety configuration.
90613, Device attribute outsize is invalid
Description
Device arg attribute outsize is empty or not a number.
Consequences
The system will stop all robot movements.
Probable causes
The safety configuration has not been created using
RobotStudio.
Recommended actions
Update the safety configuration.
90614, Could not attach device to net
Description
Attaching device arg to net arg failed because the device is
already attached to net arg.
Consequences
The system will stop all robot movements.
Probable causes
The safety configuration has not been created using
RobotStudio.
Recommended actions
Update the safety configuration.
Continues on next page
430
90615, Could not attach device to net
Description
Attaching device arg to net arg failed.
Consequences
The system will stop all robot movements.
Probable causes
The safety configuration has not been created using
RobotStudio.
Recommended actions
Update the safety configuration.
90616, Could not find device
Description
Could not find device arg.
Consequences
The system will stop all robot movements.
Probable causes
The safety configuration has not been created using
RobotStudio.
Recommended actions
Update the safety configuration.
90617, Device attribute is missing
Description
Device arg attribute arg is missing on line arg.
Consequences
The system will stop all robot movements.
Probable causes
The safety configuration has not been created using
RobotStudio.
Recommended actions
Update the safety configuration.
90618, Device attribute is invalid
Description
Device arg attribute arg is invalid on line arg.
Consequences
The system will stop all robot movements.
Probable causes
The safety configuration has not been created using
RobotStudio.
© Copyright 2005-2018 ABB. All rights reserved.
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA