Creating A Program To Enable/Disable The Manual Pulse Generator Operation - Mitsubishi Electric MELSEC-Q Series User Manual

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

11.4.4 Creating a program to enable/disable the manual pulse generator operation

Setting item
Manual pulse
[Cd.20]
generator 1 pulse
input magnification
Manual pulse
[Cd.21]
generator enable
flag
: Refer to Section 5.7 "List of control data" for details on the setting details.
Signal name
PLC READY signal
READY signal
All axis servo ON
Synchronization flag
Interface
Axis stop signal
signal
Start complete signal
BUSY signal
Error detection signal
M code ON signal
Forced stop input signal
Stop signal
External
signal
Upper limit (FLS)
Lower limit (RLS)
: If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be inserted in the
program for interlocking. If it is set to the synchronous mode, it must not be inserted in the program for
interlocking because it is turned ON when the PLC CPU executes calculation.
A sequence program must be created to execute a manual pulse generator operation.
Consider the "required control data setting", "start conditions" and "start time chart"
when creating the program.
The following shows an example when a manual pulse generator operation is started
for axis 1.
Required control data setting
The control data shown below must be set to execute a manual pulse generator
operation. The setting is carried out with the sequence program.
Setting
value
Set the manual pulse generator 1 pulse input
magnification.
1
(1 to 10000 times)
Set "1: Enable manual pulse generator
operation". (Set "0: Disable manual pulse
1 (0)
generator operation" when finished with the
manual pulse generator operation.)
Start conditions
The following conditions must be fulfilled when starting. The required conditions
must also be assembled in the sequence program, and the sequence program
must be configured so the operation will not start if the conditions are not fulfilled.
ON PLC CPU preparation completed
ON QD77GF preparation completed
ON All axis servo ON
ON
OFF Axis stop signal is OFF
OFF Start complete signal is OFF
OFF QD77GF is not operating
OFF There is no error
OFF M code ON signal is OFF
ON There is no forced stop input
OFF Stop signal is OFF
ON Within limit range
ON Within limit range
Setting details
Signal state
QD77GF buffer memory
The access is possible.
11 - 30
Chapter 11 Manual Control
Buffer memory address
4322+100n
4323+100n
4324+100n
n: Axis No.-1
Device
Y0
X0
Y1
X1
[Cd.180] Axis stop
[Md.31] Status: b14
X10 to X1F
[Md.31] Status: b13
[Md.31] Status: b12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-qd77gf4Melsec-qd77gf8Melsec-qd77gf16

Table of Contents