Mitsubishi Electric MELSEC-Q Series User Manual page 273

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Set with a hexadecimal.
Setting
H
value
Number of simultaneous starting axes
2 to 4: 2 axes to 4 axes
Set with a decimal.
Setting
K
value
Set with a decimal.
Setting
K
value
Set with a decimal.
Setting
K
value
Valid only during servo ON for all axes.
Setting value
Simultaneous starting axis No.1
0 to F: Axis 1 to Axis 16
Simultaneous starting axis No.2
0 to F: Axis 1 to Axis 16
Simultaneous starting axis No.3
0 to F: Axis 1 to Axis 16
Speed-position switching device selection
<Speed-position switching control>
0: Use the external command signal for switching
from speed control to position control
1: Use the proximity dog signal for switching
from speed control to position control
2: Use "
Cd.46
Speed-position switching command
switching from speed control to position control
<Position-speed switching control>
0: Use the external command signal for switching
from position control to speed control
1: Use the proximity dog signal for switching
from position control to speed control
2: Use "
Cd.46
Speed-position switching command
switching from position control to speed control
Speed-position switching command
<Speed-position switching control>
0: Not switch from speed control to position control
1: Switch from speed control to position control
<Position-speed switching control>
0: Not switch from position control to speed control
1: Switch from position control to speed control
Servo OFF command
0: Servo ON
1: Servo OFF
5 - 153
Chapter 5 Data Used for Positioning Control
Default
Buffer memory address
value
0000H
0
" for
" for
0
0
4339+100n
4366+100n
4367+100n
4351+100n
n: Axis No.-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-qd77gf4Melsec-qd77gf8Melsec-qd77gf16

Table of Contents