Mitsubishi Electric MELSEC-Q Series User Manual page 793

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Related buffer memory address
4375+100n
54000+20k
54002+20k
54003+20k
54004+20k
54005+20k
JOG speed
4318+100n
4319+100n
New speed value
4314+100n
4315+100n
JOG speed limit value
48+150n
49+150n
Positioning operation speed override
4313+100n
4322+100n
4323+100n
Set range
(Setting with sequence program)
<Control mode setting>
0, 10, 20
< Mark detection signal setting >
0 to 16
< Mark detection data type >
-1 to 12
< Mark detection data axis No.>
1 to 16, 801 to 804
<Mark detection data buffer memory No.>
0 to 65534
<JOG speed>
1 to 1000000000 [PLS/s]
-2
1 to 2000000000 [ 10
mm/min or another]
<New speed value>
0 to 1000000000 [PLS/s]
-2
0 to 2000000000 [ 10
mm/min or another]
<JOG speed limit value>
1 to 1000000000 [PLS/s]
-2
1 to 2000000000 [ 10
mm/min or another]
< Positioning operation speed override >
1 to 300 [%]
<Manual pulse generator 1 pulse input
magnification>
1 to 1000
16 - 47
Chapter 16 Troubleshooting
Remedy
Switch the control mode after turning BUSY OFF.
Switch the control mode after turning "Zero speed"
([Md.108] Servo status) ON.
Switch the control mode after setting a value within the
range for "[Cd.139] Control mode setting".
Carry out the control mode switching request after
completing the control mode switching.
Set a value within the setting range.
Set a value within the setting range.
Set a value with an even number within the setting
range.
Do not carry out the JOG speed change during
deceleration with the JOG start signal OFF.
Set a value within the setting range.
Set the manual pulse generator 1 pulse input
magnification to within the setting range.
k: Mark detection setting No.-1
n: Axis No.-1