When the "JOG start signal" is turned ON again during deceleration caused
by the ON
When the "JOG start signal" is turned ON again during deceleration caused by the
ON
the time the "JOG start signal" is turned ON.
Cd.181 Forward run JOG start
BUSY signal
[X10 to X1F]
Fig. 11.9 Operation when the JOG start signal is turned ON during deceleration
When the "JOG start signal" is turned ON while the test function of
GX Works2 is used
When the "JOG start signal" is turned ON while the test function of GX Works2 is
used, it will be ignored and the JOG operation will not be carried out.
In test mode flag
Cd.181 Forward run JOG start
Fig. 11.10 Operation when the JOG start signal is turned ON while the test function is used
OFF of the "JOG start signal"
OFF of the "JOG start signal", the JOG operation will be carried out from
ON
OFF
ON
OFF
JOG operation not
possible because
the test function is
being used
ON
ON
OFF
11 - 14
JOG operation not possible
because this is not the
rising edge of the JOG
start signal
OFF
Chapter 11 Manual Control
Forward run JOG operation
t
Forward run JOG
operation execution
t