[Pr.82] Forced stop valid/invalid selection
Set the forced stop valid/invalid. (Only the value specified against the axis 1 is
valid.)
All axes of the servo amplifier are made to batch forced stop when the forced stop
input signal is turned on.
The error "Servo READY signal OFF during operation" (error code: 102) does not
occur if the forced input signal is turned on during operation.
0: Valid (External input signal) ...... Forced stop (External input signal) is used.
1: Invalid ........................................ Forced stop is not used
Note1: If the setting is other than 0 and 1, the error "Forced stop valid/invalid
setting error" (error code: 937) occurs.
Note2: The "[Md.50] Forced stop input" is stored "1" by setting "Forced stop
valid/invalid selection" to invalid.
Chapter 5 Data Used for Positioning Control
5 - 37