Related buffer memory address
Same as in error codes 504, 506.
Refer to Section 5.3
"List of positioning data"
and Section 5.4 "List of block
start data"
Refer to Section 5.4
"List of block start data"
Refer to Section 5.3
"List of positioning data"
4304+100n
4300+100n
Set range
(Setting with sequence program)
<Special start instruction>
00H to 06H
<M code OFF request>
1: M code ON signal is turned OFF
<Positioning start No.>
1 to 600,
7000 to 7004,
9001 to 9004
16 - 27
Chapter 16 Troubleshooting
Remedy
Correct the positioning address.
(Refer to Section 9.2.16, 9.2.17, or 9.2.18)
In the error history, check the axis where the error other than
this error occurred, and remove the error factor. Correct the
block start data and positioning data.
Normalize the block start data.
Correct the instruction code of the special start.
(Refer to Section 5.4 [Da.13])
Correct the control method.
(Refer to Section 5.3 [Da.2])
After turning OFF the M code ON signal, start the system.
(Refer to Section 13.7.3)
Check the program which turns ON/OFF the PLC READY
signal [Y0], and turn ON the PLC READY signal. Then start
the system.
Check the READY ON signal, and then start the system.
(Refer to Section 3.3.2)
Normalize the positioning start No.
(Refer to Section 13.7.7)
n: Axis No.-1