10.3.4 Wait start

In a "wait start", the "condition data" conditional judgment designated in "[Da.14]
Parameter" is carried out for the positioning data set in "[Da.12] Start data No.". If the
conditions have been established, the "block start data" is executed. If the conditions
have not been established, the control stops (waits) until the conditions are established.
Section [2] shows a control example where the "block start data" and "positioning data"
are set as shown in section [1].
[1] Setting examples
(1) Block start data setting example
Axis 1 block
start data
1st point
2nd point
3rd point
(Note): The "condition data Nos." have been set in "[Da.14] Parameter".
(2) Positioning data setting example
Axis 1 positioning
data No.
1
2
3
10
11
12
50
[2] Control examples
The following shows the control executed when the "block start data" of the 1st
point of axis 1 is set as shown in section [1] and started.
<1> The conditional judgment set in "condition data No. 3" is carried out before
execution of the axis 1 "positioning data No. 1".
Conditions established
Go to <2>.
Conditions not established
established
<2> Execute the axis 1 "positioning data No. 10, 11, 12, and 50" and stop the
control.
Chapter 10 High-Level Positioning Control
[Da.11]
[Da.12]
Shape
Start data No.
1: Continue
1
1: Continue
10
0: End
50
[Da.1]
Operation pattern
01: Continuous positioning control
01: Continuous positioning control
00: Positioning complete
11: Continuous path control
11: Continuous path control
00: Positioning complete
00: Positioning complete
Execute positioning data No. 1, 2, and 3
Control stops (waits) until conditions are
Go to <1>.
10 - 11
[Da.13]
[Da.14]
Special start
Parameter
instruction
2: Wait start
0: Block start
0: Block start
3