Optional) Installing A Lan Switch - Huawei FusionModule2000 Installation Manual

Smart modular data center 2000 mmhigh cabinets, dual-row aisle containment, 208 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Dual-Row
Aisle Containment, 208 V)
Step 3 Tighten the captive screws in the ears using a Phillips screwdriver, and close the mounting ear
buttons.
Figure 8-7 Installing the VCN500
Step 4 Connect the VCN500 power cable to the PDU2000.
----End

8.4 (Optional) Installing a LAN Switch

Procedure
Step 1 Determine the mounting holes for the LAN switch based on the network cabinet device layout,
adjust the guide rails, and install floating nuts.
Step 2 Install the mounting ears delivered with the LAN switch and secure the LAN switch to the
rack rails in the front of the cabinet.
Issue 01 (2017-07-30)
This section describes only the installation method. The actual product appearance prevails.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Installing Monitoring Devices
128

Advertisement

Table of Contents
loading

Table of Contents