Huawei FusionModule2000 Maintenance Manual

Huawei FusionModule2000 Maintenance Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

Quick Links

FusionModule2000 Smart Modular Data Center
V100R021C00
Maintenance Guide (Fusion Module
Actuator)
Issue
01
Date
2020-12-25
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei FusionModule2000

  • Page 1 FusionModule2000 Smart Modular Data Center V100R021C00 Maintenance Guide (Fusion Module Actuator) Issue Date 2020-12-25 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    About This Document About This Document Purpose This document describes FusionModule2000 smart modular data center (FusionModule2000 for short) in terms of routine maintenance, troubleshooting, and parts replacement. It aids regular verification, maintenance and prompt solutions for device potential faults. Intended Audience This document is intended for: ●...
  • Page 4 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) About This Document Symbol Description Supplements the important information in the main text. NOTE is used to address information not related to personal injury, equipment damage, and environment deterioration. Change History Changes between document issues are cumulative.
  • Page 5: Table Of Contents

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) Contents Contents About This Document........................ ii 1 Safety Information........................1 1.1 General Safety..................................1 1.2 Personnel Requirements............................... 4 1.3 Electrical Safety..................................4 1.4 Installation Environment Requirements.......................... 6 1.5 Mechanical Safety................................... 8 1.6 Cooling System Safety.................................10...
  • Page 6 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) Contents 5.2 Replacing Power Supply and Distribution System Components................60 5.2.1 Parts Replacement for the Precision PDF........................60 5.2.2 Parts Replacement for the Integrated PDC......................60 5.2.3 Parts Replacement for the Integrated UPS.......................61 5.2.4 Parts Replacement for the SmartLi..........................
  • Page 7 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) Contents 5.4.10 Replacing a Temperature and Humidity Sensor....................105 5.4.11 Replacing a T/H Sensor (33010516)........................108 5.4.12 Replacing a Water Sensor............................111 5.4.13 Replacing an Alarm Beacon............................113 5.4.14 Replacing a UIM20A expansion module......................114 5.4.15 Replacing a FusionModule Actuator........................
  • Page 8: Safety Information

    The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
  • Page 9 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information General Requirements ● Do not install, use, or operate outdoor equipment and cables (including but not limited to moving equipment, operating equipment and cables, inserting connectors to or removing connectors from signal ports connected to outdoor facilities, working at heights, and performing outdoor installation) in harsh weather conditions such as lightning, rain, snow, and level 6 or stronger wind.
  • Page 10 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information ● All cable holes should be sealed. Seal the used cable holes with firestop putty. Seal the unused cable holes with the caps delivered with the cabinet. The following figure shows the criteria for correct sealing with firestop putty.
  • Page 11: Personnel Requirements

    Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ●...
  • Page 12 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information General Requirements Use dedicated insulated tools when performing high-voltage operations. AC and DC Power D ANGER Do not connect or disconnect power cables with power on. Transient contact between the core of the power cable and the conductor will generate electric arcs or sparks, which may cause fire or personal injury.
  • Page 13: Installation Environment Requirements

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information ● Do not perform any improper operations, for example, dropping cables directly from a vehicle. ● When selecting, connecting, and routing cables, follow local safety regulations and rules.
  • Page 14 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information vents, or feeder windows of the equipment room. Ensure that no liquid enters the equipment to prevent faults or short circuits. ● If any liquid is detected inside the equipment, immediately disconnect the power supply and contact the administrator.
  • Page 15: Mechanical Safety

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information 1.5 Mechanical Safety Hoisting Devices ● Do not walk under hoisted objects. ● Only trained and qualified personnel should perform hoisting operations. ● Check that hoisting tools are available and in good condition.
  • Page 16 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information ● When climbing a ladder, take the following precautions to reduce risks and ensure safety: – Keep your body steady. – Do not climb higher than the fourth rung of the ladder from the top.
  • Page 17: Cooling System Safety

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information ● When moving the equipment by hand, wear protective gloves to prevent injuries. ● Move or lift the equipment by holding its handles or lower edges. Do not hold...
  • Page 18: Battery Safety

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information Refrigerant Frostbite Refrigerant leakage may cause frostbite. Take protective measures (for example, wear antifreeze gloves) when handling refrigerant. Storage and Recycling ● Do not store devices near a heat source or under direct sunshine.
  • Page 19 NO TICE To ensure battery safety and battery management accuracy, use batteries provided with the UPS by Huawei. Huawei is not responsible for any battery faults caused by batteries not provided by Huawei. Battery Installation Before installing batteries, observe the following safety precautions: ●...
  • Page 20 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information Lead-acid batteries emit flammable gas when used. Ensure that batteries are kept in a well-ventilated area and take preventive measures against fire. Battery Leakage NO TICE Battery overheating causes deformation, damage, and electrolyte spillage.
  • Page 21: Others

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 1 Safety Information ● Do not throw a lithium battery in fire. ● When maintenance is complete, return the waste lithium battery to the maintenance office. 1.8 Others ● Exercise caution when shutting down the smart cooling product. Doing so may cause equipment and room overheating, which will damage the equipment.
  • Page 22: M Preparations

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 2 O&M Preparations O&M Preparations 2.1 O&M Personnel Skill Requirements Table 2-1 Skill requirements for smart module O&M personnel Field Personnel Skill Requirements Cabinet system Familiar with the overall configurations and layout of the...
  • Page 23 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 2 O&M Preparations Tool Name, Specifications, and Appearance Step ladder (2 m) Phillips Phillips Flat-head screwdriver screwdriver screwdriver (2–5 M4/M6/M8 M3/M4 (length < 100 mm) Adjustable wrench Socket wrench Hex key Box-end wrench (6")
  • Page 24 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 2 O&M Preparations Tool Name, Specifications, and Appearance Wire stripper Hydraulic pliers Wire clippers Nylon cable tie Multimeter Electroprobe Brush Hammer Vacuum cleaner Hacksaw Handsaw Right angle 13# solid wrench...
  • Page 25: Reference Documentation

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 2 O&M Preparations 2.3 Reference Documentation NO TICE The documents provided in the solution only include the special maintenance items, maintenance methods, and precautions of the components. For other maintenance items of the components, see the documents delivered with the components.
  • Page 26 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 2 O&M Preparations NO TE ● The ECC800/NetEco version depends on the version in use. Click on the ECC800/ NetEco WebUI to obtain the current version. ● For NetEco maintenance, see the NetEco documents.
  • Page 27: Routine Maintenance

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Routine Maintenance 3.1 Overview Overview Routine maintenance is a preventive measure. It refers to periodic checking and maintenance carried out to promptly identify and handle alarms and potential faults during the normal running of the system.
  • Page 28: Routine Maintenance Checklist

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance 3.2 Routine Maintenance Checklist Table 3-1 Routine maintenance checklist Item Operation Guide Standard Troubleshooting Check alarms. On the ECC800- No abnormal For details, see the Pro WebUI, choose...
  • Page 29 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Operation Guide Standard Troubleshooting Check the status ● Web Scenario: The video Check the of the video Enter the IP surveillance communication surveillance address of the...
  • Page 30: Monthly Maintenance

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance 3.3 Monthly Maintenance Table 3-2 Monthly maintenance for the power supply and distribution system Item Method Expected Result Troubleshooting UPS power grid Check the ● Input voltage: ●...
  • Page 31 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Connection of Visual ● The cables are ● Replace input and output inspection not damaged. damaged cables. cables of the PDF ● The terminals ●...
  • Page 32 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Air filter Visual The air filter is clean Remove and clean inspection and not blocked. the air filter. (Cleaning with water is recommended.)
  • Page 33 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Visual Check that the Tighten loose inspection screws on the screws. indoor fan are not loose or distorted. Table 3-4 Monthly maintenance for the management system...
  • Page 34 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting ECC800-Pro RUN Check the The RUN indicator ● If the RUN indicator (green) RUN indicator blinks slowly. indicator blinks on the fast, check...
  • Page 35: Quarterly Maintenance

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance 3.4 Quarterly Maintenance Table 3-5 Quarterly maintenance for the power supply and distribution system Item Method Expected Result Troubleshooting Operating On the ● Operating Check whether the...
  • Page 36 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Table 3-6 Quarterly maintenance for the cooling system Item Method Expected Result Troubleshooting Monitoring Export smart There are no Rectify the fault or cooling abnormal records in...
  • Page 37 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Wet film Start the Water drainage is ● If no water is humidifier equipment, normal. supplied, check choose Maint the cable > Diagnostic connection or Mode >...
  • Page 38 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Fire control Generate ● A smoke alarm ● Check whether the linkage function smoke is displayed on smoke detector or under a...
  • Page 39 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Connection of Check ● The iBOX (CIM) ● Secure the iBOX iBOX (CIM) whether the is attached (CIM) again. iBOX (CIM) firmly.
  • Page 40 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting WiFi function ● Check ● The RUN ● If the RUN indicator the RUN indicator blinks is off, check indicator at long...
  • Page 41 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Indicator on the Check The indicator If the indicator blinks smoke detector whether the blinks once every twice every 6 seconds indicator on 6 seconds.
  • Page 42 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Indicators on the Observe the ● If the PWR ● If the PWR indicator fusion module PWR, RUN, indicator is is off, check...
  • Page 43: Semiannual Maintenance

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Indicators on the Observe the ● If the PWR ● If the PWR indicator access actuator PWR, RUN, indicator is is off, check...
  • Page 44 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Oxidation of Visual inspection No metal ● If any metal metal component is component components in rusty. experiences the PDF or NMW...
  • Page 45 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Cleanliness of the Visual inspection The white paper If the white paper smart cooling that you use to turns black, clean product...
  • Page 46 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Availability On the ECC800- On the ECC800-Pro If the display is of the Pro WebUI, WebUI, you can see abnormal, check UIM20A...
  • Page 47 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Availability 1. On the The fusion module If lights cannot be of the fusion ECC800-Pro actuator controls switched on or off, module...
  • Page 48 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Availability On the ECC800- The fusion module If the skylight cannot of the fusion Pro WebUI, actuator controls be normally module choose...
  • Page 49 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Press the The emergency If the door cannot be emergency button can be used opened by pressing button to open to open the door.
  • Page 50 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Availability Observe the After the card is If the door is of the cabinet electronic swiped, the green abnormal, replace the cabinet...
  • Page 51 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting LAN switch Observe the PWR The PWR indicator Take corrective availability indicator on the is steady green. measures based on LAN switch.
  • Page 52 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting ● Steady green: The LAN switch is not running properly or is starting. ● Steady orange: The indicator is under a self-test during the startup.
  • Page 53 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Availability Drip water from A water alarm is If the water sensor is of the water the water generated on the abnormal, check...
  • Page 54 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Availability Observe the The indicator of the If the switch indicator of the smart indicator of the smart rPDU switch is off, check the...
  • Page 55: Annual Maintenance

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance 3.6 Annual Maintenance Table 3-11 Annual maintenance Item Method Expected Result Troubleshooting Battery 1. When battery The battery string 1. Rectify any connection strings are connection point...
  • Page 56 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance Item Method Expected Result Troubleshooting Battery capacity When the UPS is The test result is 1. Locate the test backed up, Pass. cause when an discharge a...
  • Page 57: Alarms And Troubleshooting

    Alarms and Troubleshooting If an incident occurs and may jeopardize the long-term stable running of the FusionModule2000, the system or a component will generate alarms. O&M personnel or the person on duty must promptly handle any identified alarms. Issue 01 (2020-12-25)
  • Page 58: Alarm Handling Flowchart

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 4 Alarms and Troubleshooting 4.1 Alarm handling flowchart Figure 4-1 Alarm handling flowchart 4.2 Viewing and Collecting Alarm Information Prerequisites An alarm is generated. NO TE Alarm information helps to rapidly locate and rectify faults.
  • Page 59: Determining The Faulty Area And Alarm Severity

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 4 Alarms and Troubleshooting Step 3 Collect alarm information. NO TE After an alarm is generated, immediately collect the following information: ● Occurrence time and place ● Detailed fault symptoms ●...
  • Page 60 ● Alarm references in documents delivered with components ● Alarm reference in this document ● Alarm reference obtained from Huawei technical support It is recommended that the alarm handling report consists of information about the alarm occurrence time, location, symptom, fault locating process, alarm handling process, and alarm prevention solutions.
  • Page 61: Parts Replacement

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Parts Replacement 5.1 CommonECC800-Pro Operations 5.1.1 Preparations and WebUI Login Prerequisites ● Supported operating system: Windows 7 and later versions ● It is recommended that the screen resolution be 1366 x 768 or higher.
  • Page 62 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TICE ● In ECC800 V100R002C10 and earlier versions, the default IP address of port WAN_1 is 192.168.1.10. ● The WAN1 port IP address cannot be set to an IP address in any of the following network segments: 192.168.0.x, 192.168.245.x, 192.168.246.x and...
  • Page 63 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-1 Adding an address Enable file download and set the security level of the trusted site to low. Figure 5-2 Setting parameters NO TE When switching between different versions of the ECC800-Pro on your PC, you are advised to clear the historical Internet Explorer cache.
  • Page 64: Performing Startup Password Authentication

    – After the first login, change the password in time to ensure account security and prevent unauthorized network attacks, such as data tampering. Huawei will not be liable for any security issues caused by your failure to change the preset password in time or password loss after changing.
  • Page 65 Save. Install the Huawei AppGallery. If the downloaded file exists in the drop- down list box, tap the file to install the Huawei AppGallery. If the downloaded file does not exist in the drop-down list box, choose File > Local on the desktop, find the Download folder, and tap the Huawei AppGallery installation package.
  • Page 66: Synchronizing The Configuration Parameters

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TE – The initial password is Changeme after WiFi is enabled. The initial password is valid only when you press the button for the first time to enable WiFi after delivery.
  • Page 67: Replacing Power Supply And Distribution System Components

    Indicator Power distribution detection module NO TE If you need to replace any other parts, contact Huawei technical support. 5.2.2 Parts Replacement for the Integrated PDC For details about parts replacement for the integrated PDC, see the "Parts Replacement" section in theECC800-Pro user manual.
  • Page 68: Parts Replacement For The Integrated Ups

    Indicator Power distribution detection module NO TE If you need to replace any other parts, contact Huawei technical support. 5.2.3 Parts Replacement for the Integrated UPS For details about parts replacement for integrated UPS, see the "Parts Replacement" section in the UPS user manual.
  • Page 69: Replacing An Rpdu

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TE If you need to replace any other parts, contact Huawei technical support. 5.2.5 Replacing an rPDU Impact on the System One power input of the equipment cannot work.
  • Page 70: Parts Replacement For The New Main Way

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement ● Material: smart rPDU of the same specifications Context The smart rPDU is installed near the rear door of the cabinet. Procedure Step 1 Open the rear door of the cabinet.
  • Page 71: Parts Replacement For The Cooling System

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Replaceable Part Output Circuit Breaker of the Power Distribution Uni NO TICE There could be service interruptions during the replacement of the new main way. If power disconnection is required, seek the customer's permission first.
  • Page 72: Parts Replacement For The Netcol500 Variable Speed Outdoor Unit

    Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TE If you need to replace any other parts, contact Huawei technical support. 5.3.2 Parts Replacement for the NetCol500 Variable Speed Outdoor Unit For details about parts replacement for the NetCol500 variable speed outdoor unit, see the "Parts Replacement"...
  • Page 73: Replacing An Ecc800-Pro Main Control Module

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement 5.4.1.1 Replacing an ECC800-Pro Main Control Module Prerequisites NO TICE ● The ECC800-Pro main control module is hot-swappable. ● Before disconnecting cables from the ECC800-Pro main control module, label the cables based on the corresponding ports.
  • Page 74: Replacing An Ecc800-Pro Psu

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Step 6 (Optional) Install the removed Micro SD and SIM card in the corresponding slot of the new ECC800-Pro main control module. Figure 5-5 Installing the Micro SD and SIM card Step 7 Install the spare ECC800-Pro main control module in the ECC800-Pro subrack and tighten the screws on both sides of the ECC800-Pro main control module.
  • Page 75: Replacing Ecc800-Pro Antennas

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-6 Replacing a PSU ----End 5.4.1.3 Replacing ECC800-Pro Antennas Prerequisites ● Tools: ESD wrist strap, ESD gloves ● Materials: Spare ECC800-Pro antennas of the same model are available and functional.
  • Page 76 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Prerequisites ● Tools: ESD wrist strap, ESD gloves ● Materials: A spare SIM card and a micro SD card of the same model are available and functional.
  • Page 77: Replacing The Management System

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-10 Installing a SIM card and a micro SD card Step 6 Install the ECC800-Pro main control module in the card slot. Step 7 Tighten the screws on both sides of the ECC800-Pro main control module.
  • Page 78: Replacing The Vcn510 Hard Disk

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TICE After removing cables, wrap exposed terminals with insulation tape and do not block cable labels. If cable labels are blocked, cables may be connected incorrectly.
  • Page 79 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Context Recommended tools and materials: Phillips screwdriver, ESD wrist strap (or ESD gloves). Procedure Step 1 Put on an ESD wrist strap (or ESD gloves) and insert the ground terminal into the ESD jack in the cabinet.
  • Page 80 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-14 Removing the upper cover of the chassis NO TE When removing the upper cover from the chassis, do not use one hand to perform this operation.
  • Page 81 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Insert the SATA and power cables into the corresponding ports on the hard disk. During cable connection, ensure that the metallic plate of the SATA cable faces upward.
  • Page 82 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement (1) No. 1 disk installation position (2) No. 0 disk installation position Push the disk to slide the two preinstalled screws into the small holes of the cucurbit holes.
  • Page 83: Replacing A Vcn520

    5 Parts Replacement Step 4 Check the hard disk indicators to determine whether the new hard disk works properly. ----End Follow-up Procedure If the new hard disk is abnormal, immediately contact Huawei technical support engineers. 5.4.2.3 Replacing a VCN520 Prerequisites ●...
  • Page 84: Replacing A Vcn540

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-20 Securing the VCN520 Step 4 Reconnect the cables to the new VCN520. Step 5 Turn on the power switch of the VCN520. Step 6 Commissioning the VCN520. If the video recording function works properly after commissioning, the VCN520 is functional.
  • Page 85: Replacing The Vcn520/Vcn540 Hard Disk

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Procedure Step 1 Turn off the power switch of the VCN540, disconnect the power supply of the VCN540, remove the cables from the VCN540, label the cables, and record the original connection positions of the cables.
  • Page 86 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Prerequisites ● The hard disk needs to be replaced. ● Data in the hard disk has been backed up. ● A spare hard disk of the same model is available and functional.
  • Page 87: Replacing An Ivs1800

    Figure 5-23 Installing a new hard disk Step 4 Observe the hard disk indicator to check whether the hard disk works properly. ----End Follow-up Procedure If the hard disk works abnormally, contact Huawei technical support. 5.4.2.6 Replacing an IVS1800 Prerequisites ●...
  • Page 88: Replacing A Hard Disk For The Ivs1800

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TICE After removing cables, wrap exposed terminals with insulation tape and do not block cable labels. If cable labels are blocked, cables may be connected incorrectly.
  • Page 89 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Procedure Step 1 Put on an ESD wrist strap (or ESD gloves) and insert the ground terminal into the ESD jack in the cabinet. Step 2 Remove the faulty hard disk.
  • Page 90 Figure 5-30 Closing the chassis cover Step 4 Observe the hard disk indicator to check whether the hard disk works properly. ----End Follow-up Procedure If the hard disk works abnormally, contact Huawei technical support. Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 91: Replacing A Camera

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement 5.4.2.8 Replacing a Camera Impact on the System The operation of the video surveillance system will be interrupted. Preparations ● Tools: ESD wrist strap, ESD gloves, step ladder, label, marker, Phillips screwdriver ●...
  • Page 92: Parts Replacement For The Access System

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-33 Removing the camera Step 4 Install the new camera and SD card. Then, set parameters and commission the camera according to the commissioning guide. Step 5 Check that the camera functions properly.
  • Page 93: Replacing An Access Control Device

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-34 Removing the access actuator Step 4 Install the reserved access actuator in the original position and connect the cables. Step 5 Synchronize the parameters of the access actuator on the ECC800-Pro WebUI.
  • Page 94: Replacing A Button

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-35 Removing the access control device Step 2 Remove cables from the old access control device and connect the cables to the new one. Step 3 Install the new access control device on the baseplate and secure the device using screws at the bottom.
  • Page 95: Replacing A Sliding Door Magnetic Lock

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Procedure Step 1 Remove the button. Lift the side panel of the door post. Remove the side panel of the door post outwards. Remove the button connection cable, the nut on the button installation position, and then the button.
  • Page 96 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-37 Components of a sliding door magnetic lock (1) Magnetic lock fastener (2) Magnetic lock (3) Magnet (4) Magnet fastener Impact on the System The access control function of the sliding door is unavailable.
  • Page 97: Replacing A Double-Door Magnetic Lock

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-38 Installing a sliding door magnetic lock Step 6 Reconnect cables to the magnetic lock based on the labels. Step 7 Verify that the sliding door magnetic lock can function properly.
  • Page 98 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-39 Removing the mounting plate of a magnetic lock cover Step 2 Remove the cables for the double-door magnetic lock from the Phoenix terminal block on the upper frame mounting kit.
  • Page 99 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-41 Installing a magnetic lock Step 5 Install the mounting plate of the magnetic lock cover, as shown in Figure 5-42. Figure 5-42 Installing the mounting plate of a magnetic lock cover Step 6 Replace the magnet.
  • Page 100 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-43 Removing a magnet (Optional) Insert the positioning pins of the magnet into the magnet using a rubber mallet, as shown in Figure 5-44. Figure 5-44 Installing positioning pins of a magnet...
  • Page 101 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-45 Installing a magnet (1) White rubber washer Step 7 (Optional) Adjust the magnet. If the magnet does not work properly after power-on, check that: The magnet provides magnetic force by attaching magnetizable iron parts to The double-door magnetic lock is aligned with the magnet face-to-face.
  • Page 102: Replacing A Door Status Sensor

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-46 Adjusting the gap ----End 5.4.3.6 Replacing a Door Status Sensor Impact on the System The cabinet door status cannot be detected. Preparations ● Tools: Phillips screwdriver, insulation tape ●...
  • Page 103: Replacing A Cabinet Electronic Lock

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-47 Removing a door status sensor Step 4 Install a new door status sensor. Step 5 Install the new door status sensor by performing the steps above in reverse order.
  • Page 104: Parts Replacement For The Intelligent Battery Monitoring System

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-48 Electronic lock Step 3 Install a new electronic lock and connect the monitoring cable to the new lock. Step 4 Log in to the ECC800-Pro WebUI and choose System Settings > Access Management.
  • Page 105 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TICE ● If the iBOX is damaged, hold down the networking switches on all the iBATs managed by the iBOX to clear present network parameters. ● If the iBOX is not damaged, hold down the iBOX networking switch to clear present network parameters.
  • Page 106: Replacing An Ibat

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Step 4 Clamp the new iBOX to the fastener. Step 5 Reconnect cables to the iBOX based on the cable labels. Step 6 Synchronize the parameters of the iBOX on the ECC800-Pro WebUI.
  • Page 107: Replacing A Smart Eth Gateway

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-52 Removing an iBAT Step 2 Secure the new iBAT on the fastener, and connect the iBAT cables. Step 3 Press the iBOX networking switch for 2 seconds. The RF_Z indicator on the iBOX changes from blinking green at long intervals to blinking green at super short intervals, which indicates that the iBOX is being networked.
  • Page 108: Replacing The Wifi Module

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Step 3 Remove the failure smart ETH gateway from the guide rails. Figure 5-53 Removing the smart ETH gateway Step 4 Install the reserved smart ETH gateway in the original position and connect the cables.
  • Page 109: Replacing A Multi-Functional Sensor

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-54 Position of the WiFi module ----End 5.4.7 Replacing a Multi-Functional Sensor Impact on the System The temperature, humidity, and smoke cannot be sensed. Preparations ●...
  • Page 110: Replacing A Smoke Detector

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TE A reserved multi-functional sensor has a base. You can replace the old base if it is damaged or does not match the buckle of the reserved multi-functional sensor.
  • Page 111: Replacing A Cabinet Temperature Sensor

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Step 4 Install the smoke detector on the control skylight. Step 5 Verify that the smoke detector function is normal. ----End 5.4.9 Replacing a Cabinet Temperature Sensor Impact on the System The cabinet temperature cannot be detected during replacement.
  • Page 112: Replacing A Temperature And Humidity Sensor

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-57 Installing temperature sensors (1) Fastener Step 4 Check that the temperature sensor works properly. ----End 5.4.10 Replacing a Temperature and Humidity Sensor Prerequisites ● A temperature and humidity (T/H) sensor needs to be replaced.
  • Page 113 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement NO TICE Exercise caution because the device is still energized after it is shut down on the controller home screen. Step 2 Open the rear door and remove the air filter.
  • Page 114 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-59 Installing a T/H sensor Step 6 Set the DIP switches of T/H sensors. Table 5-10 DIP switch setting on a T/H sensor Locati Display Name Addr DIP Switch Sequence No.
  • Page 115: Replacing A T/H Sensor (33010516)

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Locati Display Name Addr DIP Switch Sequence No. Hot aisle 1 aisle temp/humid Hot aisle 2 temp/humid Hot aisle 3 temp/humid Hot aisle 4 temp/humid Hot aisle 5 temp/humid Step 7 Install the air filter and close the rear door.
  • Page 116 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-60 Removing a T/H sensor NO TE Before installing the new T/H sensor, check that its DIP switch settings are consistent with the DIP switch settings of the old T/H sensor.
  • Page 117 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-61 Installing a T/H sensor Step 6 Set the DIP switch on the T/H sensor. Table 5-11 DIP switch settings on T/H sensors Locati Display Name Addr DIP Switch No.
  • Page 118: Replacing A Water Sensor

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Locati Display Name Addr DIP Switch No. Hot aisle 2 temp/humid Hot aisle 3 temp/humid Hot aisle 4 temp/humid Hot aisle 5 temp/humid Step 7 Install the air filter and close the rear door.
  • Page 119 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-62 Water sensor components (1) Water detector (2) Conversion cable end A, (3) Conversion cable connecting to the water detector (4) Conversion cable end B, (5) Water detection rope end A,...
  • Page 120: Replacing An Alarm Beacon

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-63 Connecting a conversion cable to a water detector Step 2 Replace a water detection cable. Remove the faulty water detection cable from the port. Install a new water detection cable.
  • Page 121: Replacing A Uim20A Expansion Module

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement ● Skill requirement: hardware installation engineers Procedure Step 1 Disconnect the terminals between the cable delivered with the alarm beacon and the ECC800-Pro communications cable. Step 2 Remove the two screws from the alarm beacon and remove the alarm beacon from the door box.
  • Page 122: Replacing A Fusionmodule Actuator

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-66 Removing a UIM20A Step 4 Secure a mounting ear to each of the two sides of the spare UIM20A expansion module using four M4 screws, and then secure the spare UIM20A expansion module to the original installation position.
  • Page 123: Replacing The Fuse For A Fusionmodule Actuator

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Procedure Step 1 Disconnect the upstream fuse for the FusionModule Actuator. Step 2 Open the cover on the front panel of the FusionModule Actuator, and disconnect the cables.
  • Page 124: Replacing A Skylight Magnetic Lock

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Impact on the System The PAD cannot be charged, the lights and rotating skylight cannot be controlled, and the aisle access control system cannot be used. Preparations...
  • Page 125: Replacing A Pad

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-68 Removing a skylight magnetic lock Step 4 Install the new skylight magnetic lock. Step 5 Connect the cable for the new skylight magnetic lock to the cascading terminal of the lock.
  • Page 126: Replacing A Pad Power Connector

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Step 5 Connect the charging cable to the reserved pad. ----End 5.4.19 Replacing a PAD Power Connector Context Item Appearance Remarks PAD power connector The BOM number is 14190892.
  • Page 127 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-69 Removing the PAD power connector holder Step 5 Disconnect cables from the power connector. Figure 5-70 Disconnecting power connector cables (BOM number: 14190892) Figure 5-71 Disconnecting power connector cables (BOM number: 14190242) Step 6 Remove the PAD power connector from its holder.
  • Page 128 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Remove the power connector from the guide rail of the holder. Figure 5-72 Removing the PAD power connector holder (BOM number: 14190892) Figure 5-73 Removing the PAD power connector holder (BOM number: 14190242) Step 7 Assemble the PAD power connector holder.
  • Page 129 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-75 Assembling the PAD power connector holder (BOM number: 14190242) Step 8 Connect cables from the power connector to the fusion module actuator, and route the cables.
  • Page 130: Replacing An Aisle Led Light

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-78 Securing the PAD power connector holder Step 10 Reinstall the charging cable for the power connector. Step 11 Reinstall the baffle plate under the power connector.
  • Page 131 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-79 Interconnecting LED light tubes Procedure Step 1 Locate a failed light. NO TE ● If an LED light does not work but the cables to the light are intact, the LED has failed and the LED light needs to be replaced.
  • Page 132: Replacing The Strip Light Of An Atmosphere Light

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Replace all failed LED light tubes until all LED light tubes in the aisle work properly. ----End 5.4.21 Replacing the Strip Light of an Atmosphere Light Impact on the System The strip light of an atmosphere light is off during replacement.
  • Page 133 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Preparations ● Tools: ESD gloves, Phillips screwdriver, step ladder, label, marker ● Materials: atmosphere light, atmosphere light power supply Figure 5-82 Positions of atmosphere light power supplies (inside the aisle)
  • Page 134: Replacing An Elight Strip Light

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement 5.4.23 Replacing an eLight Strip Light Impact on the System The eLight strip light is off during replacement. Preparations ● Tool: ESD gloves ● Material: eLight strip light Procedure Step 1 Remove three white rubber panels from the door frame.
  • Page 135: Replacing An Elight Actuator

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Step 7 Install a new strip light. Step 8 Install the new strip light by performing the preceding steps in reverse order. Step 9 On the ECC800-Pro WebUI, choose Maintenance > Opening Guide > Linkage Test >...
  • Page 136: Replacing An Elight Power Supply

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Procedure Step 1 Label each cable based on the corresponding ports on the eLight actuator. Step 2 Remove cables from the eLight actuator. Step 3 Remove the old eLight actuator from guide rails.
  • Page 137: Replacing A Smart U Space Manager (Connected To A Uim20A Expansion Module)

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-85 Positions of the eLight actuator and power supply (inside the aisle) (1) eLight actuator (2) eLight power supply (3) Upstream fuse Procedure Step 1 Disconnect the upstream fuse for the eLight power supply.
  • Page 138 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Preparations ● Tools: ESD gloves, label, marker ● Material: smart U space manager Figure 5-86 Smart U space manager installation diagram (main control box attached to the top of the cabinet interior)
  • Page 139 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-87 Installing a smart U space manager (main control box attached to the top of the cabinet exterior) (1) Fastener (2) UIM20A Expansion Module (3) Main control box...
  • Page 140: Common Maintenance Tasks

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement 5.5 Common Maintenance Tasks 5.5.1 Operating a Hydraulic Circuit breaker (Inside the Smart rPDU) Hydraulic circuit breakers are important components of the smart rPDU. Power-on Operation Step 1 When the circuit breaker is OFF, press the button in the direction of the arrow to set the circuit breaker to ON.
  • Page 141: Handling Long-Time Hotspot At The Air Inlet Of A Cabinet In Icooling Mode

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement Figure 5-89 Power-off operation ----End 5.5.2 Handling Long-time Hotspot at the Air Inlet of a Cabinet in iCooling Mode Symptom There is a hotspot (higher than 27°C) at the air inlet of a cabinet in iCooling mode for more than 2 hours and the hotspot persists.
  • Page 142: A Acronyms And Abbreviations

    FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) A Acronyms and Abbreviations Acronyms and Abbreviations alternating current AC transfer switch BCB-BOX battery circuit breaker box battery interface module bypass bus synchronization controller communication interface module direct current energy control center Issue 01 (2020-12-25) Copyright ©...
  • Page 143 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) A Acronyms and Abbreviations energy control module economy control operation Ethernet iBAT iBattery integrated circuit Internet technology liquid crystal display light emitting diode miniature circuit breaker monitor display unit NetEco...
  • Page 144 FusionModule2000 Smart Modular Data Center Maintenance Guide (Fusion Module Actuator) A Acronyms and Abbreviations secure digital memory subscriber identity module video cloud node uninterruptible power system WiFi Wireless Fidelity Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd.